7.4.2 B24BKNE
Fig. 34: Wiring example for attachment B24BKNE
BN
Brown L (+)
BU
Blue N (–)
①
Supply voltage
②
2-wire cable (signal)
The actuator and the control module are factory wired.
Connect the supply voltage to the connecting cable (approx. 1 m, with ferrules). 2-wire cable for signals
(terminals 6 and 7).
Technical data for the actuator,
Technical data for the control module
Order code detail
B24BKNE
Control module
BKNE230-24
Nominal voltage
AC 230 V 50/60 Hz
Functional range
AC 198...264 V
Rating
19 VA (including actuator)
Power consumption
10 W (including actuator)
Mains cable
Cable, 1 m (free of halogens, without plug)
2-wire cable
Recommended cable
Screw terminals for wires, 2 x 1.5 mm²
JE-H (St) Bd FE180/E30-E90
IEC protection class
II (protective insulation)
Ambient temperature (normal operation)
–30...+50 °C
Storage temperature
–40...+80 °C
Electrical connection
Actuator with control module > B24BKNE
Smoke control damper Type EK2-EU
49