background image

5.6  Suspending the smoke control

damper

5.6.1  General

Smoke control dampers can be suspended from solid

ceiling slabs using adequately sized threaded rods.

Load the suspension system only with the weight of the

smoke control damper.

Ducts must be suspended separately.

Suspension systems longer than 1.5 m require fire-

resistant insulation.

Size of threaded rods

Thread M8 M10 M12 M14 M16 M20

Fmax [N] per

threaded rod

219 348 505 690 942 1470

Maximum

loading [kg] per

threaded rod

22

35

52

70

96

150

5.6.2  Fixing the unit to the ceiling slab

Fig. 15: Fixing to the ceiling slab

1

Fire-rated anchor (with suitability certificate)

2

Push through installation

Use only fire-rated steel anchors with suitability certifi-

cate. Instead of anchors, you can use threaded rods

and secure them using nuts and washers.

5.6.3  Suspended installation

Fig. 16: EK-JS suspension with suspension bracket

Smoke control damper EK-JS

Suspension bracket (accessory 18, 19)*

Self-tapping screws (supply package of suspension

bracket)

Threaded rod M12

Washer M12, galvanised steel

Nut M12, galvanised steel

* When a cover grille is used, the suspension bracket

can be attached rotated by 180°.

Fig. 17: Suspended installation

Smoke control damper

Threaded rod 

Ä

 ‘Size of threaded rods’  

on page  36

Hilti mounting rail MQ 41 × 3 or equivalent

Hilti MQZ-L drilled plate or equivalent

Galvanised steel nut

Additional suspension (only if necessary)

Installation

Suspending the smoke control damper   > Suspended installation

 

Smoke control damper EK-JS

36

Summary of Contents for EK-JS

Page 1: ...oke control damper EK JS Installation and operating manual Read the instructions prior to performing any task according to EN 12101 8 tested to EN 1366 10 Declaration of performance DoP EK JS 001 GB e...

Page 2: ...the original Valid from 01 2022 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Germany Phone 49 0 2845 2020 Fax 49 0 2845 202 265 E mail trox trox de Internet http www troxtechnik com 0...

Page 3: ...nt Copying content Translating content Microcopying content Saving content to electronic systems and editing it TROX Technical Service To ensure that your request is processed as quickly as possible p...

Page 4: ...if not avoided may result in property damage ENVIRONMENT Environmental pollution hazard Tips and recommendations Useful tips and recommendations as well as informa tion for efficient and fault free o...

Page 5: ...d of a vertical duct 32 5 5 Solid smoke extract duct 34 5 5 1 On a vertical solid duct 34 5 6 Suspending the smoke control damper 36 5 6 1 General 36 5 6 2 Fixing the unit to the ceiling slab 36 5 6 3...

Page 6: ...odifying the smoke control damper or using replacement parts that have not been approved by TROX is not permitted Incorrect use WARNING Danger due to incorrect use Incorrect use of the smoke control d...

Page 7: ...Technical clarification with TROX required for some sizes Closed damper leakage EN 1751 Class 2 Nominal size B H 840 x 480 Class 3 Casing leakage EN 1751 Class B Nominal size B H 840 x 480 Class C EC...

Page 8: ...the CE marking was affixed 7 Year of manufacture 8 Manufacturer s address 9 Notified body 10 Regulated characteristics the fire resistance class depends on the application and may vary 5 1 Installati...

Page 9: ...0 400 450 520 550 600 680 700 750 840 850 900 950 1000 1050 1100 1150 1200 1250 100 125 150 165 320 480 640 800 960 1120 1280 1440 1600 1760 1920 2080 2240 2400 2560 15 Nm BEN 25 Nm BEE 40 Nm BE techn...

Page 10: ...0 400 450 520 550 600 680 700 750 840 850 900 950 1000 1050 1100 1150 1200 1250 100 125 150 165 320 480 640 800 960 1120 1280 1440 1600 1760 1920 2080 2240 2400 2560 15 Nm BEN 25 Nm BEE 40 Nm BE techn...

Page 11: ...ide B Width H Height B x H nominal size area exposed to the airflow Keep area free for accessibility of the actuator Fixing option for control module Fixing with self tapping screws 4 2 x 9 5 mm to be...

Page 12: ...28 29 30 31 32 33 34 35 35 36 37 960 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 42 1120 22 23 24 25 27 28 29 30 31 32 33 34 36 37 38 39 40 42 43 44 45 46 1280 24 25 27 28 29 30 32...

Page 13: ...of the supply package unless stated otherwise but has to be provided by others it has to be suitable for the installation situation Transport on site If possible take the product in its transport pac...

Page 14: ...K JZ or EK2 EU on solid shaft wall EK JZ or EK2 EU on a vertical smoke extract duct shaft EK JZ or EK2 EU on a horizontal smoke extract duct EK JS in a horizontal smoke extract duct EK JS at the end o...

Page 15: ...entilation can be enabled in combined systems with smoke control dampers Depending on the system layout the damper blade can be fully opened fully closed or in the intermediate position Depending on w...

Page 16: ...d i o S 28 in a vertical duct E600 120 hod i o S 30 at the end of a vertical duct 32 Vertical solid smoke extract ducts Operating temperature up to 600 C on a vertical duct E600 120 ved i o S 34 LE As...

Page 17: ...zontal or lying down The position of the actuator is not critical but it must remain accessible for maintenance 5 3 1 High temperature sealing tape High temperature sealing tape is used to seal betwee...

Page 18: ...ing tempera tures Hexagon bolts M8 with 2 washers and nuts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided...

Page 19: ...ape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the sheet...

Page 20: ...Hexagon bolts M8 with 2 washers and nuts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Duct cl...

Page 21: ...ape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the sheet...

Page 22: ...tures Hexagon bolts M8 with 2 washers and nuts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others D...

Page 23: ...o the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the sheet stee...

Page 24: ...Hexagon bolts M8 with 2 washers and nuts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Duct cl...

Page 25: ...ape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the sheet...

Page 26: ...or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Suspension bracket fixed with 2 self tapping screws 5 6 Suspending the smoke contro...

Page 27: ...tions 2 Apply HT sealing tape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke c...

Page 28: ...Hexagon bolts M8 with 2 washers and nuts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Duct cl...

Page 29: ...tape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the shee...

Page 30: ...ts to be provided by others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Suspension bracket fixed with 2 self tapping...

Page 31: ...ctions 2 Apply HT sealing tape to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke...

Page 32: ...others Duct clips or self tapping screws 5 5 x 22 mm to be provided by others HT sealing tape accessories or to be provided by others Suspension bracket fixed with 2 self tapping screws 5 6 Suspendin...

Page 33: ...to the flange of the smoke control damper for sealing 3 Manufacture suspension for smoke control damper 5 6 Suspending the smoke control damper on page 36 4 Screw smoke control damper to the sheet ste...

Page 34: ...thers Flange to be provided by others 54 HT sealing tape to be provided by others Self tapping screws 4 2 x 16 mm to be provided by others Wallplug with fire safety engineering certification and threa...

Page 35: ...e flange to be provided by others to the EK JS with self tapping screws 3 For sealing stick the HT sealing tape onto the flange 4 Drill the holes on the shaft wall according to the hole pattern on the...

Page 36: ...ion Use only fire rated steel anchors with suitability certifi cate Instead of anchors you can use threaded rods and secure them using nuts and washers 5 6 3 Suspended installation Fig 16 EK JS suspen...

Page 37: ...mper is not affected connection according to assembly and operating manual of the smoke control damper The sizing of the smoke extract duct used remains the responsibility of the system installer and...

Page 38: ...The flexible connectors should meet the specifications for the sheet steel smoke extract duct Be sure to follow the manufacturer s instructions 6 2 Cover grilles Fig 20 EK JS with a cover grille EK JS...

Page 39: ...lication it must be ensured that the con tacts of the auxiliary switches can no longer be used in the milliampere range once they have been wired up to a relatively high current A combination of mains...

Page 40: ...W 12 W Power consumption when idle 0 1 W 0 5 W Power consumption rating 6 VA 5 VA 18 VA 8 2 A Imax 5 ms 8 2 A Imax 5 ms Torque 15 Nm 25 Nm 40 Nm Run time 30 s 90 60 s 90 60 s 90 Limit switch Type of...

Page 41: ...when idle 0 4 W 0 5 W Power consumption rating 7 VA 6 VA 15 VA 4 A Imax 5 ms 7 9 A Imax 5 ms Torque 15 Nm 25 Nm 40 Nm Run time 30 s 90 60 s 90 60 s 90 Limit switch Type of contact 2 changeover contact...

Page 42: ...on observe the following instructions Chapter 7 2 Wiring and connection to the central BMS on page 39 Technical data of continuously controlled actuators Order code detail B24 SR Actuator BEN24 SR TR...

Page 43: ...dividually or as part of an overall system and according to the control matrix set up for the event of a fire In this case the control system of the mechan ical smoke extract system or pressurisation...

Page 44: ...Technical data for the control module Order code detail B24A B24AM B24AS Control module AS EM EK AS EM M AS EM SIL2 Supply voltage 26 5 31 6 V DC Current consumption 450 mA 450 mA 400 mA from AS i Max...

Page 45: ...ical data for the control module Order code detail B24BKNE Control module BKNE230 24 Nominal voltage AC 230 V 50 60 Hz Functional range AC 198 264 V Rating 19 VA including actuator Power consumption 1...

Page 46: ...factory wired Technical data of the actuator 7 3 2 B230 on page 41 Chapter 7 3 1 B24 on page 40 Connection data Order code detail B24C Control module BC24 G2 Supply voltage Provided by the SLC con tro...

Page 47: ...module BRM 10 F ST BRM 10 F Electrical data Supply voltage 18 32 V DC typically 24 V Current consumption 5 mA typically 26 mA max for 100 ms when relays close Protection level IP 20 EN 60529 IEC prote...

Page 48: ...conductors Solid core 0 2 1 5 mm Multi strand without ferrule 0 2 1 5 mm Multi strand insulated ferrule 0 25 0 75 mm Multi strand non insulated ferrule 0 25 1 5 mm Ambient conditions Ambient temperat...

Page 49: ...oes not impair the function of the damper The damper blades seals adapt themselves to the seal and can compensate for the smallest devia tions Important Install the smoke control damper without tor si...

Page 50: ...mpers are installed country specific regulations may apply Maintenance The smoke control damper and the actuator are mainte nance free with regard to wear but smoke control dampers must still be inclu...

Page 51: ...r for damage Smoke control damper damper blades and seal have to be intact Repair or replace the smoke control damper Specialist personnel Functional test of the smoke control damper 8 2 Functional te...

Page 52: ...h off the power supply before working on any electrical equipment 1 Disconnect the wiring 2 Remove the smoke extract ducts 3 Remove the smoke control damper Disposal ENVIRONMENT Risk of harm to the en...

Page 53: ...Decommissioning removal and disposal Smoke control damper EK JS 53...

Page 54: ...11 Flange dimensional drawing Flange dimensional drawing Smoke control damper EK JS 54...

Page 55: ...de Pba Spacing of the outer holes on width side Nba Pitch of the outer holes on width side K Sum of the distances of the outer holes on height side Pha Spacing of the outer holes on height side Nha Pi...

Page 56: ...ion in a horizontal smoke extract duct 18 20 22 24 32 in a vertical smoke extract duct 30 on a vertical smoke extract duct 28 on a vertical solid smoke extract duct 34 on solid shaft walls 34 Installa...

Page 57: ...Smoke control damper EK JS 57...

Page 58: ...Smoke control damper EK JS 58...

Page 59: ...Smoke control damper EK JS 59...

Page 60: ...Valid from 01 2022 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Ger many Germany Phone 49 0 2845 2020 49 0 2845 202 265 E mail trox trox de http www troxtechnik com...

Reviews:

Related manuals for EK-JS