1 - General Information

1.1  Introduction

This installation, operation and maintenance manual is intended for

active chilled beam Type DID301 and DID302.

Y

ou must read all instructions prior to the installation, operation or

maintenance of this product.  Take special note of the information that
is accompanied by the symbols  described in section 1.3 below.

The DID301 and DID302 active chilled beams are designed for

dealing with high internal thermal loads using a combination of air

and water. This is achieved by using primary air delivered via

ductwork and chilled water delivered via pipe work from the central

plant, directly to the beam. Primary air is ducted to the upper air

chamber via a side or top inlet. The primary air is then discharged

through nozzles to a lower section containing a 2- or 4-pipe heat

exchanger coil. This causes room air to be induced via the unit’s face

panel, up and through the heat exchanger coil. The cooled (or

heated) room air is then mixed with the primary air before being

delivered back to the space through the beam’s discharge slot(s).

The beam uses the primary air energy to induce air through the coil;

it does not contain any moving parts, fans or motors.

1.2  Safety

The customer must use qualified personnel and follow all applicable

building codes and safety regulations when installing, commissioning

and performing maintenance of this product.  Eye protection, gloves

and hard hat should be worn at all times when handling the product.

Consult all local building, occupational safety and other codes appli-

cable to the installation.

Please pay particular attention to the symbols used throughout the

manual that indicate safety related issues, warnings and important

notices or information; read the complete manual before  installation

and be familiar with the meaning of the safety symbols in the next

section 1.3.

1.3 Symbols used in this manual

When reading this manual, particular attention must be given to the

parts marked with the following symbols:

1.4  Receiving, Inspection and Storage

All TROX products are inspected and tested prior to shipment to

ensure the highest quality.  Chilled beams are packed individually in

cardboard cartons.  

Upon receipt of the chilled beam shipment, conduct a thorough

inspection of the outer packaging and pallets for possible damage.  If

damage has occured during shipping, indicate the damaged items

on the delivery papers immediately and inspect the chilled beams

contained in those containers for damage.

If damage has occurred during shipping, immediately file a claim with

the carrier.

Refer to the 

Manufacturer’s Representations and Warranties

(included in each carton and on page 11 of this manual) for detailed

handling instructions and damage reporting procedures.

Beams should be stored in a clean and dry location.  If beams remain

packaged as delivered (strapped and wrapped on pallet), they can

be stored as delivered (do not stack pallets).  If packaged beams are

removed from pallet, they should not be stacked more than four high.

Packaging is not suitable for outside storage.

Warning!

Indicates a potentially dangerous situation for the

product and the environment

Important!

Designation of a danger that can cause personal

injury or damage to property.

Note

Indicates important notices or information

!

Fragile

Handle with care.  The chilled beam should not be

handled using the water pipes or damage to the coil

assembly may result!

Note

Chilled beam should not be removed from its

individual carton for storage.  Beams should not be

unpacked until they have been moved to the

installation location and just before installation is to

begin (see details on pages 4-5).

Summary of Contents for DID301

Page 1: ...Installation Operation and Maintenance Manual Active Chilled Beams Type DID301 and DID302 OM US DID301 302 6...

Page 2: ...ng and venting the water system 7 3 8 Typical installations 7 Commissioning 4 1 Waterside commissioning 8 4 2 Airside commissioning 8 4 3 Airside commissioning tables 8 9 Maintenance 5 1 Cleaning inst...

Page 3: ...ngs and important notices or information read the complete manual before installation and be familiar with the meaning of the safety symbols in the next section 1 3 1 3 Symbols used in this manual Whe...

Page 4: ...hoses recommended for water connections from assembly to the supply and return water circuits unless factory furnished flexible hoses are included with product order or hard connections 3 Precautions...

Page 5: ...direction The unit is provided with sliding hanging brackets that allow for adjustment along the length and width of the beam both shown here Guidelines when using rods Install Unistrut with appropria...

Page 6: ...he final water connections STEP THREE Make water connections If NPT connections apply do NOT over tighten applying excessive force on the water pipes may damage the heat exchange coil NOTE See section...

Page 7: ...ontinuous venting is necessary The installation of both manual and automatic venting systems is recommended The pump should only be started when filling is complete To remove all air from the system t...

Page 8: ...rimary air chamber in W G DID301 302 Installation Operation Maintenance Manual USA 06 2015 Open pressure cap Min bending radius 3 2 Flexible hose For water connection NPT Female swivel thread for conn...

Page 9: ...e locked position To clean the beam face If necessary the face of the beam and visible painted surfaces can be cleaned using a mild detergent diluted with warm water Apply with a soft cloth rinse and...

Page 10: ...sign figure Obstruction on induction grille or heat exchanger coil Remove induction grille and inspect clean grille and heat exchanger as necessary Air connection detached from beam Inspect attachment...

Page 11: ...t any such covered defect or to replace or exchange the Product Customer shall bear all shipping and handling expenses related to the return of the Products Any repaired corrected replaced or exchange...

Page 12: ...Maintenance Manual USA 06 2015 TROX USA Inc 4305 Settingdown Circle Cumming Georgia 30028 Phone 770 569 1433 Fax 770 569 1435 E Mail trox troxusa com www troxusa com U S Edition 2015 DID301 302 Insta...

Reviews: