1
Safety
1.1 Correct use
The electronic control component type Compact XM0 •
XS0 is used in combination with a TROX VAV terminal
unit TVE for constant volume flow control in ventilation
and air conditioning systems.
The control component is designed for use in internal
spaces.
Supply air area of application
Conditions for use
Control com-
ponent
The usual conditioning in ventilation
and air conditioning systems allows
use in the supply air without additional
dust protection measures.
XM0
Extract air area of application
Conditions for use
Control com-
ponent
Extract air with a low content of dust
or lint (e. g. office) without additional
dust protection measures.
XM0
XS0
For dry extract air with higher dust or
lint content, without additional dust
protection measures.
XS0
For extract air with a high proportion of
dust, lint or sticky components or for
exhaust air with aggressive media
without additional dust protection
measures.
XS0
In unspecified applications or in com-
bination of contaminated air (e. g.
dust) with humidity.
XS0
Do not use VAV terminal units in extract air systems in
commercial kitchens unless the extract air has been
cleaned as much as possible with high-efficiency aer-
osol separators; see VDI 2052.
Incorrect use
WARNING!
Danger of injury or risk of damage to property
due to incorrect use!
Misuse of the control component can lead to dan-
gerous situations.
Never use the control component/device:
–
in explosion-proof areas
–
in aircraft
–
outdoors without sufficient protection against the
effects of weather
–
for areas of application that are not described in
this manual
Modifying the unit or using replacement parts that have
not been approved by TROX is not permitted.
1.2 Safety signs
The following symbols and signs are usually found in
the work area. They apply to the very location where
they are found.
WARNING!
Danger due to illegible signage!
Over time, stickers and signs may fade or become
otherwise illegible, meaning that hazards cannot be
identified and necessary operating instructions
cannot be followed. There is then a risk of injury.
–
Ensure that all of the safety, warning and oper-
ating information is clearly legible.
–
Replace illegible signs or stickers immediately.
Electrical voltage
Only skilled qualified electricians are allowed to work in
areas marked as having electrical voltage.
Unauthorised people must not enter areas, open cabi-
nets or work on components where an electrical voltage
is present and which are hence marked with this
symbol.
Safety
Safety signs
Control component Compact XM0 • XS0 for VAV terminal unit TVE
6