12
EN
multiple socket outlet PV4-MID-PS
Settings pages
1. Press the multifunction button (16) for 2 s if you have
currently selected the access page
Menu / settings
.
ð
The sequence regarding the assigned counter will be
displayed.
2. Press the multifunction button (16) for 3 s.
ð
The elements identifying counter and starting value
(e.g. kWh) are flashing.
3. Press the multifunction button (16) once to change the
counter that is to be assigned to the output.
4. In order to deactivate the output, press the button several
times until
dis
will be displayed.
5. Press the multifunction button (16) for 2 s to confirm the
setting.
6. Press the multifunction button (16) for 2 s to reset the
partial counter.
ð
The elements identifying the counter will start flashing.
7. In order to exit the settings pages again, press the
multifunction button (16) for 2 s.
ð
A confirmation sequence will be displayed.
8. Press the multifunction button (16) once to change the
value. Select
Y
to exit and save the changes and
N
to exit
without saving the changes. Select
C
to continue browsing
the
Menu / settings
.
9. Briefly press the multifunction button (16) to confirm your
selection.
Zugangseite zum Menü /
Einstellungen
Zugewiesener Zähler
Teilzähler zurücksetzen
Verlassen der Einstellseiten
Cleaning
Warning of electrical voltage
Before any work on the device, remove the mains plug
from the mains socket!
Hold onto the mains plug while pulling the power cable
out of the mains socket.
Clean the device with a soft, damp and lint-free cloth. Ensure
that no moisture enters the housing. Protect electrical
components from moisture. Do not use any aggressive cleaning
agents such as cleaning sprays, solvents, alcohol-based or
abrasive cleaners to dampen the cloth.
Wipe the housing dry after cleaning.
Errors and faults
The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.
The residual current device trips:
First carry out a visual check of the multiple socket outlet and
the connected devices.
There is
a defect
on the multiple socket outlet or on the
connected consumer:
•
Take the defective multiple socket outlet out of operation
and do not use it any longer.
•
Take the connected defective device out of operation and
do not use it any longer.
Have the connected device and / or the multiple socket outlet
checked by a qualified electrician.
There is
no defect
on the multiple socket outlet:
•
Switch the residual current device (7) back on.
The residual current device trips repeatedly:
Carry out the following steps for verifying the defect:
•
Carry out a function test of the multiple socket outlet by
checking it according to the Maintenance chapter without
a device being connected.
•
If the residual current device (7) does not trip when
actuating the test button
T
(2), do not use the multiple
socket outlet any longer. Have it checked by a qualified
electrician.
•
If the residual current device (7) trips when actuating the
test button
T
(2), switch the residual current device (7)
back on again and connect the device to the multiple
socket outlet. If the residual current device (7) then trips
again, take the device out of operation and have it checked
by a qualified electrician.