EN
11
spot cooling air conditioning unit PT 5300 SP
No. Designation
Meaning
20
Ventilation
LED
Illuminated when
ventilation
mode is
activated
21
Mode
button
Selecting the operating mode:
Room air cooling
Spot cooling operation
Ventilation
Dehumidification
22
Spot cooling
mode
LED
Is lit when the
Spot cooling
mode is
activated
23
Room air cooling
LED
Is lit when the
Room air cooling
mode is
activated
24
Speed
button
Setting the fan speed
25
Fan speed
LEDs Indication of the fan speed
I
= low
II
= high
26
On/off
button
Switching the device on or off
27
On/off
LED
Operating control lamp
28
Environment
segment
indication
Indicates the actual temperature.
Indicates error codes E1, E2 and E3
Warning of electrical voltage
Risk of electric shock!
The device does not have the appropriate protection
class for use in wet rooms.
There is a risk of electric shock!
Never use the device in wet rooms (e.g. in bathrooms
and laundry rooms) and never immerse the device in
water!
Switching the device on
1. Once you have completely installed the device as
described in the Start-up chapter, you can switch it on.
2. Press the
On/Off
button (
26
).
ð
The device starts in the
Room air cooling
mode.
ð
The
Room air cooling
LED (
23
) is illuminated.
Setting the operating mode
•
Room air cooling
•
Spot cooling operation
•
Ventilation
•
Dehumidification
Room air cooling
In the
Room air cooling
mode the room will be cooled down to
the desired target temperature.
The temperature to be set is the room temperature and is
measured at the air inlet.
1. Press the
Mode
button(
21
) until the
Room air
cooling
LED (
23
) is lit.
2. Press the
Decrease value
(
14
) or
Increase value
button (
13
)
to select the desired target temperature. The temperature
can be adjusted in increments of 1 °C in a range between
15 °C and 35 °C.
ð
The desired target temperature is indicated on the
segment display (
12
).
3. Press the
fan speed
button (
24
) to set the desired fan
stage.
ð
The
fan speed
LED (
25
) for the desired fan stage will be
illuminated.
ð
The
room air cooling
LED (
23
) will be illuminated to
indicate
cooling
mode.
Spot cooling operation
Info
The outlet temperature is measured at the air outlet
inside the device. You set the temperature at which the
air is blown out of the cold air ducts. It is
recommended to set the target temperature approx.
10 °C below the desired temperature. If, for example,
you would like to achieve 12 °C, set the target
temperature to 2 °C.
In the
Spot cooling
mode, a specific spot or area in the room is
cooled.
1. Press the
Mode
button(
21
) until the
Spot air
cooling
LED (
22
) is lit.
2. Press the
Increase value
(
14
) or
Decrease value
button (
13
)
to select the desired target temperature. The temperature
can be adjusted in increments of 1 °C in a range between
0 °C and 20 °C.
Ventilation
1. Press the
Mode
button (
21
) until the LED for
ventilation
(
20
) lights up.
2. Press the
fan speed
button (
24
) to set the desired fan
speed.
ð
The LED for the selected fan speed (
25
) will be
illuminated.
Dehumidification
In
dehumidification
mode the humidity level in the room is
reduced.
The target temperature can be set to obtain a cooling effect
during dehumidification.
1. Press the
Fan speed
button(
24
) and the Mode button (
21
)
simultaneously for 3 seconds until an acoustic signal
sounds and the
Spot cooling
LED (
22
) flashes.
ð
Dehumidification
mode is selected.
ð
In the segment indication, the actual temperature is
shown on the left-hand side and the target temperature
is shown on the right-hand side.
2. To exit the
Dehumidification
mode, keep the
Fan
speed
button (
24
) and Mode button (
21
) pressed
simultaneously for 3 seconds.