background image

T900pi

7

W-006-A

WARNING!

THIS APPLIANCE MUST BE EARTHED

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 

protection must conform with BS 7671 (IEE 

wiring regulations) and be sufficient for the 

amperage required.

The following notes are for guidance only:
1

 

The shower must only be connected to a 

230-240V ac supply. If you are installing a

shower with a kilowatt rating above 9kW, it 

is advisable to contact the local electricity 

supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 

connection within the installation make 

sure that no terminal is live. If in any doubt, 

switch off the whole installation at the mains 

supply and remove the correct fuse.

3

 The shower must be connected to its own 

independent electrical circuit. 

IT MUST NOT

 

be connected to a ring main, spur, socket 

outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 

has a main switch rating of 80A or above 

and that it has a spare fuse way which will 

take the fuse or Miniature Circuit Breaker 

(MCB) necessary for the shower 

(Fig.4)

.

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 

installation will not be straightforward and 

may require a new consumer unit serving 

the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 

carry out what is necessary. 

  For close circuit protection 

DO NOT

 use a 

rewireable fuse. Instead use a suitably rated 

Miniature Circuit Breaker (MCB) or cartridge 

fuse 

(see Table A)

.

5.1

  A 30mA residual current device (RCD) 

MUST

 be installed in all UK electric and 

pumped shower circuits. This may be part of 
the consumer unit or a separate unit.

Triton Showers,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

xxxx

Fig.3

Summary of Contents for T900pi

Page 1: ...t in use This is a safety procedure recommended for all electrical appliances The showerhead and hose supplied with this product are a safety critical part of your shower Failure to use genuine Triton parts may cause injury and invalidate your guarantee IMPORTANT Under NO circumstances must this shower be connected directly to a mains water supply It is designed for GRAVITY FED COLD WATER systems ...

Page 2: ...connected to any tap or fitting other than those specified This appliance must not be connected to the water mains supply and not connected by a hose set A suitable double pole isolation switch for supply disconnections must be incorporated in the fixed wiring circuit in accordance with current wiring rules See Electrical Installation section for further details Minimum inlet pressure 0 08 metres ...

Page 3: ...gulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be flushed to clear debris before connecting to the shower unit 2 3 DO NOT solder pipes or fittings within 300mm of the shower unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of outlet flow co...

Page 4: ...ead is not blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and backplate and possibly damage the sealing rubber This book contains all the necessary fitting and operating instructions for your Triton pumped electric shower Please read them carefully and keep for future reference The shower installation must be carr...

Page 5: ... Sound Power Level db 55 INTRODUCTION IMPORTANT SAFETY INFORMATION GENERAL GUIDANCE NOTES please read SPECIFICATIONS GENERAL ADVICE TO USERS Main components 6 Electrical requirements 7 8 Water requirements 9 Siting of the shower 10 Fitting the shower to the wall 11 12 Plumbing connections 13 Electrical connections 14 Commissioning 15 16 Operating the shower 17 18 Operating functions 19 Instruction...

Page 6: ...rmal safety cut out main 8 Terminal block 9 Can and element assembly 10 Power selector 11 Pressure switch 12 Temperature valve 13 Solenoid valve 14 Earth connection 15 Rear pipe cable entry area 16 Inlet elbow 17 Outlet pipe 18 Filter Inside cover fig 2 19 Start Stop switch Fig 2 NOTE Not all wires have been depicted for reasons of clarity 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 5 5 ...

Page 7: ...ch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet lighting circuit or cooker circuit 3 1 The electrical supply must be adequate for the loading of the unit and existing circuits 4 Check your consumer unit main fuse box has a main switch rat...

Page 8: ... bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD 8 The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided by the s...

Page 9: ...e The supply pipe from the cistern should be on the opposite side to the float operated valve to prevent air being drawn into the pipe when the cistern is filling If it is intended to operate the shower in hard water areas above 200 ppm temporary hardness a scale inhibitor should be fitted Fig 5 shows a typical system layout DO NOT use jointing compounds on any pipe fittings for the installation M...

Page 10: ... It is important that the wall surface is flat otherwise difficulty may be encountered when fitting the cover and subsequent operation of the unit may be impaired IMPORTANT Water regulations It is required that the showerhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray ...

Page 11: ...ovals If a top entry is required for the water pipe remove the top cut out in the backplate fig 8 and rotate the inlet elbow so that it points upward If a bottom entry is required for the cold water pipe then a hole will need to be cut out of the cover fig 9 and the inlet elbow rotated to face downward If entry is required from the back rotate the inlet elbow upwards and fit the supplied elbow to ...

Page 12: ...out of square adjustment after the plumbing connections have been completed Note A temporary factory fitted locking screw is fitted to the power selector spindle fig 12 This is to make sure the spindle is held in the COLD position while the commissioning procedure is carried out DO NOT remove the locking screw before this procedure is completed Fig 10 Fig 11 IMPORTANT DO NOT TURN SELECTOR SPINDLE ...

Page 13: ...he isolating stopvalve to the cistern Drain the cistern IMPORTANT The pipework must be brought direct from the cold water storage cistern with no other cold water draw offs between the shower and the cistern Fit the pipework to the inlet elbow Make sure the elbow collet is fully engaged with the pipe Although the pipework connection to the shower is via 15mm diameter pipework on long runs use 22mm...

Page 14: ...minal marked N Live cable to terminal marked L IMPORTANT Fully tighten the terminal block screws and check that no cable insulation is trapped under the screws Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through con...

Page 15: ...tor to the COLD position fig 16 DO NOT remove the locking screw fitted to the power selector spindle fig 17 it can be removed only when the commissioning procedure has been completed Make sure the water supply is still turned on to the shower Open the bleed screw on the pump unit fig 18 by rotating one revolution When water flows from the drain pipe this indicates that any trapped air is vented an...

Page 16: ...ooth flow of water to be obtained while air and any debris is being flushed from the shower When a smooth flow of water is obtained rotate the temperature control from 1 to 10 several times fig 21 to release any trapped air within the unit Once flushing out has been completed stop the water flow by pressing the START STOP button SWITCH OFF THE ELECTRICITY SUPPLY TO THE SHOWER AT THE ISOLATING SWIT...

Page 17: ...ing the temperature control at this setting will only increase or decrease the force of the water from the showerhead It will not alter the water temperature Red outline symbol is the LOW setting for extra economy during hot months Temperature adjustment at this setting is via the temperature control Single red symbol is the MEDIUM setting for economy during warmer months and any temperature adjus...

Page 18: ...ckwise towards the lower numbers will increase the water flow To increase the shower temperature Turning the temperature control clockwise towards the higher numbers will decrease the water flow Note Be certain the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few seconds between selecting a flow rate and...

Page 19: ...oled sufficiently power to the elements will be automatically restored to the previous setting at the time of interruption Safety cut out The unit is fitted with a non resettable over temperature safety device In the event of abnormal operation which could cause unsafe temperatures within the unit the device will disconnect the heating elements It will require a visit from a qualified engineer to ...

Page 20: ...and wash under running water Make sure all debris etc is removed Replace by pushing the unit back into its housing until the threads engage and then turn fully clockwise until tight DO NOT OVERTIGHTEN Before replacing the cover it is strongly advised to prime the unit by opening the bleed screw until water drains from it Close the bleed screw and connect the plug to the cover Replace the cover and...

Page 21: ...230V 84500660 6 Selector switch 82500180 microswitch wire assy 7 Connecting pipe 7052556 8 Flow valve assembly 82100300 9 Solenoid 22009120 10 Inlet pipe assembly 82800600 11 Outlet pipe 83314640 12 Filter 82800620 13 Cover assembly c w knobs button 82500270 14 Terminal block wires 82201160 Start stop switch 83305380 Pressure relief device 82800450 Ref Description Part No 1 2 3 4 14 5 6 7 8 9 10 1...

Page 22: ...Start Stop button is pressed check the consumer unit fuse or circuit breaker or isolating switch If blown or faulty renew or reset as applicable If it fails again consult a competent electrician 1 2 1 Remove the cover and ensure the plug and socket are firmly connected 1 3 1 Have solenoid checked by a competent electrician or contact Customer Service 1 4 1 If the power neon is lit when the Start S...

Page 23: ...filter is not blocked First isolate the electricity supply and then remove the cover 6 1 2 Check the cold water cistern is full 6 1 3 Make sure the water supply pipe is not blocked or air locked 6 1 4 Check there is no simultaneous demand from the cistern during showering 6 1 5 Reprime the unit without electricity switched on to the unit see commissioning section 7 1 1 Clean or replace blocked car...

Page 24: ...stomer Service Spares Department on 01 628 6711 Payment should be made by credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify your requirements using the Information contained in the user guide Triton...

Reviews: