Power Shower
14
LIVE CONNECTION
(Brown or Red Wire)
NEUTRAL CONNECTION
(Blue or Black Wire)
Fig.17
ELECTRICAL CONNECTIONS
This product does not require earthing, however,
the supply cable must conform to relevant
tables in current IEE regulations. In most cases
0.75 mm² twin cable
If replacing an existing Triton Power Shower
then the floating earth can still be terminated at
the product terminal block.
ENSURE THE ELECTRICITY SUPPLY IS
SWITCHED OFF AT THE ISOLATING SWITCH.
Cable entry points are shown in
fig.2
.
Route the cable into the shower, taking care to
avoid the area of the wall fixings and connect to
the terminal block
(fig.17)
as follows:
Neutral cable to terminal marked
N
Live cable to terminal marked
L
Earth cable (If present) to terminal marked
E
IMPORTANT:
Make sure wires are within the
terminal block clamps and not undernreath.
Fully tighten the terminal block screws and
check that no cable insulation is trapped
under the screws or clamps.
Note:
Fuses do not ensure user protection
against electric shock. In the interest of electrical
safety, all mains electric and pumped showers
should be fitted with a 30mA residual current
device (RCD). This may be part of the consumer
unit or a separate unit.
DO NOT switch on the electricity supply until
the water has been turned on to the unit and
connections have been tested for leaks.