Triton ASPIRANTE Installation And Operating Instructions Manual Download Page 7

Aspirante Remote electric shower

5

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 

non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by 

installers to determine the approximate  

size of the incoming cable.

1.

  Measure the width of an individual strand, 

and half that measurment to find 

(r)

,  

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

  Multiply 

(r) x (r)

 x 

3.14,

  

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

  Multiply this by the number of wire strands 

(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

  The number obtained would suggest  

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily accessible 
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations, the cable 

will unavoidably be placed in one or more 
of the above conditions. This being so, it is 
strongly recommended to use a minimum 
of 10mm cabling throughout the shower 
installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Summary of Contents for ASPIRANTE

Page 1: ...2180300L January 2014 Installation and operating instructions Aspirante remote shower Installers please note these instructions are to be left with the user...

Page 2: ...9 Guarantee service policy etc rear cover Aspirante Remote electric shower To check the product suitability for commercial and multiple installations please contact Triton s specification advisory ser...

Page 3: ...to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation must comply with Water Regulations Building Regulations or any part...

Page 4: ...re taken during the installation will give a long trouble free life from your shower SPECIFICATIONS Electrical Nominal power Nominal power rating at 240V rating at 230V 8 5kW 40A MCB rating 7 8kW 40A...

Page 5: ...afety cut out main 13 Earth connection 14 Control cable clamp 15 Thermal cut out outlet 16 Outlet pipe 17 Transformer 18 Connector socket 19 Stepper motor 20 Trimplate Control panel Fig 2 21 Control c...

Page 6: ...y doubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring ma...

Page 7: ...h body while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket...

Page 8: ...ked Note If the stated flow rate is not available it may not be possible to achieve optimum performance from the unit throughout the year The water supply can be taken from a cold water storage cister...

Page 9: ...ment but if the showerhead can be placed within a bath basin or shower tray then a double check valve or a similar device must be fitted in the supply pipework to prevent back flow Pressure relief saf...

Page 10: ...xing template Fig 8 Place the template on the wall and mark the position of the 15 mm hole Drill and channel a route as required Place and position the control cable between the remote pack and contro...

Page 11: ...th towels sheets etc IMPORTANT The remote pack MUST be mounted vertically DO NOT MOUNT IT HORIZONTALLY Procedure Unscrew the top and bottom retaining screws Fig 10 and lift the cover from the backplat...

Page 12: ...entry is required for the mains cold water then the necessary hole will need to be cut out in the trimplate and cover Fig 13 If a surface cable entry from the top is required then the relevant hole in...

Page 13: ...n of the water supply to the inlet of the remote pack flush out the pipework to remove all swarf and system debris To do this connect a hose to the pipework and turn on the mains water supply long eno...

Page 14: ...ct line of any spray when in use The end fittings consist of an 8mm copper pipe designed to slide flush into the water pipe to provide support and a push fit connector fig 16 Push on the fittings to b...

Page 15: ...PRD tube is clear IMPORTANT Do not bend either the PRD tube or heated water pipe sharply as they will kink and restrict the water flow If a tight bend is required in the heated water pipe cut the pipe...

Page 16: ...finished surface The connector can be cut to size if required The threaded connector should protrude from the wall surface between 8 mm and 13 mm Make good the wall The bulkhead and its cover are supp...

Page 17: ...ucture it may be preferable to secure the bulkhead by applying a bead of silicon seal to the back of the bulkhead Apply PTFE tape to the threaded connector Screw the bulkhead assembly onto the threade...

Page 18: ...Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit or i...

Page 19: ...remove the access panel Fig 28 to reveal the connector socket Cable entry into the remote pack is through one of the built in cut outs Remove the protective dust covers from both ends of the control c...

Page 20: ...implate and secure with the two screws Before replacing the cover check on the PCB that the purge pin is located on its two pins the factory set position see Fig 34 Locate the tags on the cover into t...

Page 21: ...the high economy cold and low pressure This flashing sequence lasts about twenty seconds All lights will then go out except the Start Stop surround indicating the power is on to the unit Press the Sta...

Page 22: ...ce it on one of the pins Replacing the remote pack cover Locate the tags on the cover into the holes on the backplate and guide into position Secure the cover in position with the three retaining scre...

Page 23: ...the high button LED will light and water will begin to flow To stop the shower Press the Start Stop button The phased shutdown will start and water will cease to flow after a few seconds Note the but...

Page 24: ...the temperature control anti clockwise Fig 36 This will increase the flow of water through the shower and is indicated by lower numbers To increase the shower temperature Turn the temperature control...

Page 25: ...each control button there is an LED which lights up when the button is pressed visually showing which shower mode is in operation Phased shutdown In use when the Start Stop button is pressed power is...

Page 26: ...off at the isolation switch to avoid the unit being accidentally switched on IT IS IMPORTANT TO KEEP THE SHOWERHEAD CLEAN TO MAINTAIN THE PERFORMANCE OF THE SHOWER The hardness of the water will dete...

Page 27: ...mpetent person SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS The inlet filter is situated inside the solenoid inlet Fig 39 To gain access to the filter remove the cover then disconnect and remove the...

Page 28: ...7072985 4 Thermal cut out main 22009860 5 Heater can assembly 8 5kW 84500300 9 5kW 84500290 10 5kW 84500670 6 Stabiliser valve assembly 82600780 7 Stepper motor 82300170 8 Control cable clamp 7051655...

Page 29: ...old effect 87400050 16 All thread fitting 7032915 17 Control panel mounting bracket 7012512 18 Bulkhead assembly white 85500170 chrome effect 85500180 gold effect 85500190 19 Heated water pipe fitting...

Page 30: ...rhead clean or replace blocked sprayplate cartridge 2 2 1 Check if stop taps are fully open Check if blockage in inlet filter 2 3 1 Switch to economy power setting and readjust flow rate to give requi...

Page 31: ...7 2 Twisted blocked flexible shower hose 7 3 Showerhead not removed while commissioning 4 3 1 Switch to full power setting and readjust the flow rate via the temperature control to give required temp...

Page 32: ...including post code the model number and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor...

Reviews: