Specifications
Supports Tripp Lite's Watchdog system service to restore operation to locked equipment through soft
reboot of application/OS or hard power off/on reboot of connected equipment, ideal for unattended kiosk
applications
●
Built-in grounding lug
●
Hot swappable user battery replacement
●
Optional PDUBHV10 bypass PDU enables hot-swappable UPS replacement with no disruption to
connected equipment
●
Space saving, ultra-compact housing with support for wall-mount, desktop or floor placement
●
OVERVIEW
UPC Code
037332123138
UPS Type
Line-Interactive
INPUT
Rated input current (Maximum Load)
10A
Nominal Input Voltage(s) Supported
230V AC
UPS Input Connection Type
C14 inlet
UPS Input Connection Description
Attached 15cm line cord with C14 inlet. The C14 inlet accepts user-supplied AC power cord with country specific
plug.
UPS Input Cord Length (ft.)
0.5
UPS Input Cord Length (m)
0.2
Input Phase
Single-Phase
OUTPUT
Output Volt Amp Capacity (VA)
750
Output Watt Capacity (Watts)
450
Nominal Voltage Details
230V nominal output in battery mode
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
Automatic frequency selection
Output Voltage Regulation (Line
Mode)
+8%, -21%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Included Output Power Cables
Includes 2 C13 to C14 output power cables
UPS Output Receptacles (Surge
Suppression Only)
3 UPS outlets, 3 surge-only outlets
Hot-Swap PDU options
PDUBHV10 (2U / 8 C13 outlets)
Output AC Waveform (AC Mode)
Sine wave
2 / 5