background image

Output Volt Amp Capacity
(VA)

600

Output Watt Capacity
(watts)

425

Nominal Output Voltage(s)
Supported

115V; 120V

Frequency compatibility

60 Hz

Output voltage regulation
(line mode)

-18%, +8%

Output voltage regulation
(Battery mode)

115V (+/- 5%)

Built-in UPS output
receptacles

6 5-15R outlet(s)

Surge suppression only
outlets

3 UPS outlets, 3 surge-only outlets

Output AC waveform (AC
mode)

Sine wave

Output AC waveform
(battery mode)

PWM sine wave

INPUT

Rated input current (at
maximum load)

12A

Nominal Input Voltage(s)
Supported

120V AC

UPS input connection type

5-15P

UPS Input cord length (ft.)

6

UPS Input cord length (m)

1.8

Recommended Electrical
Service

15A 120V

BATTERY

Full load runtime (minutes)

9 min. (600w)

Half load runtime (minutes)

22 min. (300w)

DC system voltage (VDC)

12

Battery recharge rate
(included batteries)

Less than 6 hours from 10% to 90%

Replacement battery
cartridge (internal UPS
battery replacement)

RBC52

 (quantity 2)

Battery Access

Battery access door

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147

Overvoltage correction

Input voltages between 128 and 147 are reduced by 12%

Undervoltage correction

Input voltages between 93 and 107 are boosted by 14%

Summary of Contents for TE600

Page 1: ...ervoltages as high as 147 saving battery reserves for use only during complete power failures Unique design features 6 protected outlets 3 UPS supported 3 surge suppression only diagnostic LEDs and a built in serial port that works with PowerAlert Software and cabling to provide automatic unattended shutdown of network and PC applications part 75 0195 200 000 Ultimate Lifetime Insurance USA Canada...

Page 2: ...t connection type 5 15P UPS Input cord length ft 6 UPS Input cord length m 1 8 Recommended Electrical Service 15A 120V BATTERY Full load runtime minutes 9 min 600w Half load runtime minutes 22 min 300w DC system voltage VDC 12 Battery recharge rate included batteries Less than 6 hours from 10 to 90 Replacement battery cartridge internal UPS battery replacement RBC52 quantity 2 Battery Access Batte...

Page 3: ...Yes PHYSICAL Installation form factors supported with included accessories Tower Installation form factors supported with optional accessories Wallmount UPSWM tower mounting kit Primary form factor Tower UPS Power Module dimensions in primary form factor height x width x depth inches 10 8 x 5 2 x 7 5 UPS Power Module dimensions in primary form factor height x width x depth cm 27 3 x 13 3 x 19 UPS ...

Page 4: ...dwide 2 year limited warranty Connected Equipment Insurance U S Canada Puerto Rico 200 000 Ultimate Lifetime Insurance Related Items Optional Products Product Type Related Model Description Qty Audio Cables CT120 Instant Read AC Outlet Circuit Tester 1 Extended Warranties WEXT3 OMNI 3 Year Extended Warranty For OmniSmart OmniPro OmniVS 1 Extended Warranties WEXT5 OMNI 5 Year Extended Warranty For ...

Page 5: ...ne at www tripplite com en products model cfm txtModelID 66 Copyright 2012 Tripp Lite All rights reserved All trademarks are the sole property of their respective owners Tripp Lite has a policy of continuous improvement Specifications are subject to change without notice Photos may differ slightly from final products ...