The drawing below shows bypass utility input
A
, UPS isolation input
B
, and UPS isolation output
C
termination points. The bypass output
D
is
prewired to the distribution panel, which reduces installation time. Use
the attached table as a wiring guideline subject to NEC and local codes.
Flexible cable and conduit is recommended for ease of installation.
Access panels are located on the side and rear of the bypass enclosure for
access to termination points.
Wiring
Front View
Side View
C
B
A
D
Tripp Lite P/N
Voltage
DP Poles DP
Breaker MBP
MBP
Breaker KAIC Rating Cable Size
SUDC208V42P
208Y/120V
42
225A
-
-
10
000 AWG
SUDC208V42P30M 208Y/120V
42
225A
20 &
30kVA
100A
18
4 AWG
SUDC208V42P40M 208Y/120V
42
225A
40kVA
150A
65
2 AWG
SUDC208V42P60M 208Y/120V
42
225A
60kVA
225A
65
000 AWG
SUDC208V84P60M 208Y/120V
84
225A
60kVA
225A
65
000 AWG
Wiring Guidelines