3. Condenser Installation (Outdoor Unit)
Figure 3-7: Condenser Mounting Interface (side mounted, bottom view looking up), SRCOOLDXRW25 (vertical installation)
3.6 Condenser Pad
If installing the condenser on the ground, provide a cement pad that extends at least 2 in. (50 mm) from all sides of the
condenser.
Note:
For colder weather installations, make sure to keep the condenser off of the ground.
Refer to local codes for pad height and other condenser pad requirements.
48.8 in.
(1240 mm)
9.8 in.
(250 mm)