background image

UPS Shipping dimensions
(height x width x depth /
inches)

16 x 14.8 x 19.8

UPS Shipping dimensions
(height x width x depth /
cm)

40.6 x 37.5 x 50.2

Shipping weight (lbs)

58.8

Shipping weight (kg)

26.7

UPS housing material

Polycarbonate

Cooling method

Fan

ENVIRONMENTAL

Operating Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full
load)

347.2

Battery mode BTU / hr. (full
load)

812.9

Audible Noise

Audible Noise < 47dBA At Front Side 1 Meter

COMMUNICATIONS

Communications interface

USB; DB9 Serial; Contact closure

Network monitoring port
description

Supports detailed monitoring of UPS and site power conditions; 2 USB ports, 1 DB9 serial and 1 DB9 contact
closure port (4 total)

PowerAlert software

Included

Communications cable

2 USB and 2 DB9 cables included

WatchDog compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

2-4 milliseconds

Low voltage transfer to
battery power (setpoint)

79

High voltage transfer to
battery power (setpoint)

147

SPECIAL FEATURES

Cold Start (startup in
battery mode during a
power failure)

Cold-start operation supported

High availability UPS
features

Hot swappable batteries

Green & high efficiency
features

Individually controllable load banks

CERTIFICATIONS

Summary of Contents for SmartPro VS SMART2200VS

Page 1: ... cabling Instruction manual Features 2200VA 1600 watt output capacity accommodates a variety of server networking and telecom devices High power density 2 2kVA UPS system occupies only 106 square inches of floor space with a height of only 14 25 inches Compatible with North American 120V 60 Hz power as found in the USA Canada and Mexico Offers 7 minutes runtime with a full load of 2200VA and 19 mi...

Page 2: ...Watt Capacity watts 1600 Output kW capacity 1 6 Output power factor 0 7 Nominal Output Voltage s Supported 120V Frequency compatibility 60 Hz Output voltage regulation line mode 18 8 Output voltage regulation Battery mode 5 Built in UPS output receptacles 7 5 15R outlet s 2 5 15 20R outlet s Built in controllable switched load banks Three switchable two outlet 5 15R load banks Output AC waveform A...

Page 3: ...s indicate line power battery power overload voltage regulation and battery low replace status Alarms Audible alarm indicates power failure overload and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status Switches 2 Switches control off on power status and alarm cancel self test op...

Page 4: ...ications interface USB DB9 Serial Contact closure Network monitoring port description Supports detailed monitoring of UPS and site power conditions 2 USB ports 1 DB9 serial and 1 DB9 contact closure port 4 total PowerAlert software Included Communications cable 2 USB and 2 DB9 cables included WatchDog compatibility Supports Watchdog application OS and hard reboot restart options for remote applica...

Page 5: ... contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SNMP Accessories SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 Software WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 Surge Protectors DCATV Network Surge Suppressor Essential protection for TV VCR coaxial lines 1 Surge Protectors DNET1 Network Surge Suppressor Essential protection for data and commu...