UPS Shipping dimensions
(height x width x depth /
inches)
18 x 11.8 x 13.5
UPS Shipping dimensions
(height x width x depth / cm)
45.7 x 29.8 x 34.3
Shipping weight (lbs)
46.2
Shipping weight (kg)
21
Cooling method
Fan
UPS housing material
PVC
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
175.4
Battery mode BTU / hr. (full
load)
454.4
COMMUNICATIONS
Communications interface
USB; DB9 Serial
Network monitoring port
description
Supports detailed monitoring of UPS and site power conditions
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
2-4 milliseconds
Low voltage transfer to
battery power (setpoint)
75
High voltage transfer to
battery power (setpoint)
147
SPECIAL FEATURES
Cold Start (startup in
battery mode during a
power failure)
Cold-start operation supported
High availability UPS
features
Hot swappable batteries
Green & high efficiency
features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A