5

“ON/OFF/STANDBY” 

Button

• To turn the UPS ON:

with the UPS plugged into a live AC wall outlet*, press

and hold the “ON/OFF/STANDBY” button for one second.** Release the
button. If utility power is absent, you can “cold-start” the UPS (i.e.: turn it ON
and supply power for a limited time from its batteries***) by pressing and
holding the “ON/OFF/STANDBY” button for one second.**

• To turn the UPS OFF:

with the UPS ON and receiving utility power, press

and hold the “ON/OFF/STANDBY” button for one second.** Then unplug
the UPS from the wall outlet. The UPS will be completely OFF.

* After you plug the UPS into a live AC outlet, the UPS (in ”Standby” mode) will automatically charge
its batteries, but will not supply power to its outlets until it is turned ON. ** The alarm will beep once
briefly after the indicated interval has passed. *** If fully charged.

“MUTE/TEST”

Button

To Silence (or “Mute”) UPS Alarms:

briefly press and release the

MUTE/TEST button.*

To Run a Self-Test:

with your UPS plugged in and turned ON, press and hold

the MUTE/TEST button. Continue holding the button until the alarm beeps sev-
eral times and the UPS performs a self test. See “Results of a Self-Test” below.
Note: you can leave connected equipment on during a self-test. Your UPS, how-
ever, will not perform a self-test if the UPS is not turned on (see
“ON/OFF/STANDBY” Button description).

CAUTION! Do not unplug your UPS to test its batteries. This will remove
safe electrical grounding and may introduce a damaging surge into your
network connections.

Results of a Self-Test:

The test will last approximately 10 seconds as the

UPS switches to battery to test its load capacity and battery charge. 

• If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm

continues to sound after the test, the UPS’s outlets are overloaded. To
clear the overload, unplug some of your equipment and run the self-test
repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit red
and the alarm is no longer sounding.

CAUTION! Any overload that is not corrected by the user immedi-
ately following a self-test may cause the UPS to shut down and cease
supplying output power in the event of a blackout or brownout.

• If the “BATTERY WARNING” LED remains lit and the alarm continues

to sound after the test, the UPS batteries need to be recharged or
replaced. Allow the UPS to recharge continuously for 12 hours, and 
repeat the self-test. If the LED remains lit, contact Tripp Lite for service.
If your UPS requires battery replacement, visit www.tripplite.com to
locate the specific Tripp Lite replacement battery for your UPS.

* The alarm will beep once briefly after the indicated interval has passed.

Basic Operation

Buttons (Front Panel)

200603172 93-2443 SmartPro update OM.qxd  5/16/2006  3:15 PM  Page 5

Summary of Contents for SmartPro SLT SMX1050SLT

Page 1: ...tion 3 Basic Operation 5 Storage and Service 8 Español Copyright 2006 Tripp Lite All rights reserved SmartPro is a trademark of Tripp Lite SmartPro SLT Intelligent Line Interactive UPS System 220 230 240V Pure Sine Wave Input Output Not suitable for mobile applications 9 Battery Replacement 8 Français 17 Optional Installation 4 Deutsch 25 PyccŞèé 33 ...

Page 2: ...C generator the generator must provide filtered frequency regulated computer grade output Equipment Connection Warnings Do not use Tripp Lite UPS Systems for life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device Do not connect surge suppressors or extension cords to the output of yo...

Page 3: ...output receptacle Plug your equipment into the UPS Plug your equipment into the UPS Repeat Step 3 above using the additional power cord s that came with the UPS Note Additional interconnection cords C13 to C14 are available from Tripp Lite Call 773 869 1234 Part P004 006 Your UPS is designed to support computer equipment only You will overload the UPS if the total VA ratings for all the equipment ...

Page 4: ...e Tripp Lite PowerAlert Software appropriate to your computer s operating system Telephone Network Protection Jacks Your UPS has jacks that protect against surges over a telephone line or a network dataline Using telephone or network data cables connect your wall jack to the UPS jack marked IN Connect your equipment to the UPS jack marked OUT Make sure the equipment you connect to the UPS s jacks ...

Page 5: ...ver will not perform a self test if the UPS is not turned on see ON OFF STANDBY Button description CAUTION Do not unplug your UPS to test its batteries This will remove safe electrical grounding and may introduce a damaging surge into your network connections Results of a Self Test The test will last approximately 10 seconds as the UPS switches to battery to test its load capacity and battery char...

Page 6: ...f a blackout or brownout BATTERY CHARGE LEDs when the UPS is operating from utility power the LEDs indicate the approximate charge state of the UPS s internal batteries red indicates the batteries are beginning to charge yellow indicates the batter ies are roughly midway through charging and green indicates the batteries are fully charged When the UPS is operating from battery power during a black...

Page 7: ... with PoE Power Over Ethernet applications Voltage DIP Switches These switches enable the UPS to be set to match actual input voltage If the Voltage DIP Switches are set above or below input voltage the UPS will treat the input as a continuous overvoltage or undervolt age condition and will automatically adjust input voltage to match the Voltage DIP Switch setting This will cause constant unnecess...

Page 8: ...ial to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid Mark the RMA number on the outside of the package If the UPS System is within the 2 year warranty period enclose a copy of your sales receipt Return the UP...

Page 9: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com ...

Reviews: