Tripp Lite SmartPro Rackmount SMX500RT1U Features And Specifications Download Page 3

DC system voltage (VDC)

12

Battery recharge rate
(included batteries)

Less than 4 hours from 10% to 90%

Replacement battery
cartridge (internal UPS
battery replacement)

RBC62-1U

Battery Access

Battery access door

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 187

Undervoltage correction

Input voltages between 187 and 207 are boosted by 14%

LEDS ALARMS & SWITCHES

LED Indicators

5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status

Alarms

Audible alarm indicates power-failure, overload and low-battery conditions

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

480 joules

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form factors
supported with included
accessories

4 post 19 inch rackmount (mounting rail kit included); 2 post 19 inch rackmount (mounting rail kit included)

Primary form factor

Rackmount

UPS / Power Module
dimensions in primary
form factor (height x width
x depth / inches)

1.7 x 17.5 x 11.8

UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)

4.4 x 44.4 x 29.8

Rack Height

1U

UPS / Power Module
weight (lbs)

18

UPS / Power Module
weight (kg)

8.2

UPS Shipping dimensions
(height x width x depth /
inches)

5 x 22.5 x 16

UPS Shipping dimensions
(height x width x depth /
cm)

12.7 x 57.2 x 40.6

Summary of Contents for SmartPro Rackmount SMX500RT1U

Page 1: ...eous power off of UPS and connected equipment in the case of fire or emergency situation Multi function audible alarms and set of 5 front panel LEDs offer at a glance notification of UPS and line power status Network grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges and line noise Attractive all black color scheme Package Includes SM...

Page 2: ...e mode 8 15 Output voltage regulation Battery mode 5 Built in UPS output receptacles 6 C13 outlet s Included output power cables Two 1 8m IEC320 C13 to C14 load jumper cables Surge suppression only outlets 6 UPS outlets 1 surge only outlets Built in controllable switched load banks One switchable single outlet C13 load bank Output AC waveform AC mode Sine wave Output AC waveform battery mode PWM s...

Page 3: ... operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status Switches 2 Switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 480 joules EMI RFI AC noise suppression Yes PHYSICAL Installation form factors supported with included accessories 4 post 19...

Page 4: ...upports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time 2 4 milliseconds Low voltage transfer to battery power setpoint 187 High voltage transfer to battery power setpoint 264 SPECIAL FEATURES Grounding lug Back panel grounding lug Cold Start startup in battery mode during a power failure Cold start operation supported High availa...

Page 5: ...r distribution for critical networking equipment 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 U022 010 10 ft USB2 0 A B Gold Device Cable A Male to B Male 1 WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 MODBUSCARD For remote monitoring and control via MODBUS protocol 1 More information including related products owner s manuals and additional technical specif...