capacity and combinations of the two (all parallel installations must be performed by a Tripp Lite authorized technician)

Full-time sine wave output with less than 3% output THD

High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input THD (THDi)

Less than 4% input THD (THDi) reduces installation costs by allowing 1:1 generator sizing

Extremely efficient operation (up to 97%) saves energy and reduces BTU output

Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges

Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems

Wide input voltage correction range: 173-300V / 276-477V AC

Pre/-1% output voltage regulation

4 available battery modules (BP480V55, BP480V78, BP480V103 and BP480V140) are housed in a separate, stand-alone hardwired external battery

compartment (Battery modules sold separately) 

Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed

Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS

Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server

Accessory slot accepts an optional internal SNMPWEBCARD and MODBUSCARD accessory options

Emergency Power Off button turns UPS output OFF and disables Bypass output

Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

80000

Output kVA capacity (kVA)

80

Output Watt Capacity (watts)

64000

Output kW capacity

64

Output power factor

0.8

Output Capacity Details

Two open power module slots enable installation of up to two additional 20kVA power modules for increased
capacity to 120kVA (authorized technician required)

Crest Factor

3:1

Nominal Output Voltage(s)
Supported

220/380V; 230/400V; 240/415V; 3-Phase Wye

Nominal Voltage details

Less than 3% output THD

Frequency compatibility

50 / 60 Hz

Output voltage regulation (line mode)

+/- 1%

Output voltage regulation (Battery
mode)

+/- 1%

Built-in UPS output receptacles

Hardwire

Output AC waveform (AC mode)

Pure Sine wave

Output AC waveform (battery mode)

Pure Sine wave

2 / 5 

 