background image

Frequency
compatibility details

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)

Output voltage
regulation (line
mode)

+/- 2%

Output voltage
regulation (Economy
line mode)

+/- 10%

Output voltage
regulation (Battery
mode)

+/- 2%

Built-in UPS output
receptacles

Hardwire

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V)

Nominal Input
Voltage(s) Supported

200V AC; 208V AC; 220V AC; 230V AC; 240V AC

UPS input
connection type

Hardwire

UPS input
connection
description

3 wire single phase input (L1, L2, G)

Recommended
Electrical Service

50A

BATTERY

Full load runtime
(minutes)

5.5 min. (7200w)

Half load runtime
(minutes)

13.5 min. (3600w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery
pack compatibility

BP240V10RT3U

BP240V557C-1PH

BP240V787C-1PH

BP240V1037C-1PH

BP240V1407C-1PH

DC system voltage
(VDC)

240

Battery recharge
rate (included
batteries)

Less than 6 hours from 10% to 90%

Battery replacement
description

Hot-swappable, user replaceable external battery packs

VOLTAGE REGULATION

Voltage regulation
description

2% output voltage regulation in standard online, double-conversion mode

Overvoltage
correction

Corrects overvoltages up to 300V

Summary of Contents for SmartOnline SU8000RT3UHW

Page 1: ...deal for advanced networking applications in data centers computer rooms network closets and rugged industrial locations Package Includes SU8000RT3UPM 3U UPS power module BP240V10RT3U external battery...

Page 2: ...contact closure outputs for custom event notification Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification requires removal of US...

Page 3: ...UPS input connection type Hardwire UPS input connection description 3 wire single phase input L1 L2 G Recommended Electrical Service 50A BATTERY Full load runtime minutes 5 5 min 7200w Half load runt...

Page 4: ...rolling LCD functions bundled PDU includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantaneous EMI RFI AC noise suppres...

Page 5: ...width x depth inches 39 8 x 31 5 x 23 UPS Shipping dimensions height x width x depth cm 101 x 80 x 58 4 Shipping weight lbs 331 Shipping weight kg 150 3 UPS housing material Steel Cooling method Fan...

Page 6: ...FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Economy mode operation Optional economy mode enables high efficiency bypass operation with a maximum...

Page 7: ...STRMKITHD Enables 2 Post Rackmount Installation of 3U and Larger UPS Transformer and Battery Pack Components 1 SNMP Accessories ENVIROSENSE Monitors temperature humidity and contact closure inputs Req...

Reviews: