Nominal Voltage details
Voltage selection via front panel LCD interface
Frequency compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy
line mode)
+/- 10%
Output voltage regulation (Battery
mode)
+/- 2%
Built-in UPS output receptacles
6 C19 outlet(s)
Output circuit breaker
20A double-pole (x6) protects 1 C19 outlet each
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum
load)
46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V)
Nominal Input Voltage(s) Supported
200V AC; 208V AC; 230V AC; 240V AC
UPS input connection type
Hardwire
UPS input connection description
3 wire single phase input (L1, L2, G)
Recommended Electrical Service
50A
Voltage compatibility (VAC)
200; 208; 230; 240
Phase
Single-Phase
BATTERY
Full load runtime (minutes)
5.5 min. (7200w)
Half load runtime (minutes)
13.5 min. (3600w)
Expandable battery runtime
Supports extended runtime with optional external battery packs
External battery pack compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC system voltage (VDC)
240
Battery recharge rate (included
batteries)
Less than 6 hours from 10% to 90%
Battery replacement description
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation description
2% output voltage regulation in standard online, double-conversion mode
Overvoltage correction
Corrects overvoltages up to 300V
Undervoltage correction
Corrects undervoltages as low as 100V
3 / 7