Tripp Lite SmartOnline SU750XL Specifications Download Page 3

Battery recharge rate

4-6 hours to 90%

Replacement
Battery Cartridge

RBC24-SUTWR

VOLTAGE REGULATION

Voltage regulation
description

On-line, double-conversion power conditioning maintains output within 2% of 120V at all times

Overvoltage
correction

Maintains output of 120V +/-2% during overvoltages to 138VAC

Brownout correction

Maintains output of 120V +/-2% during undervoltages to 80VAC

Severe brownout
correction

Maintains output of 120V +/-2% during undervoltages to 65VAC (during load conditions of 70% or less)

LEDS ALARMS & SWITCHES

Front panel LEDs

14 status LEDs offer LINE POWER, ONLINE, BYPASS, ON BATTERY, OVERLOAD, BATTERY LOW, REPLACE
BATTERY and FAULT status information. Also includes 4 LED meters for LOAD LEVEL/BATTERY LEVEL display
(Battery level readout requires pressing power on/test switch)

Alarms

Multi-function audible alarm offers notification of UPS start, backup operation, low battery warning, overload, UPS fault
and remote shutdown

Switches

Includes combination main power on/test and main power off switch

SURGE / NOISE SUPPRESSION

AC suppression
response time

Instantaneous

Dataline
suppression

RJ45 1-line tel/DSL/Ethernet

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Shipping weight
(lbs)

34.2

Shipping weight (kg)

15.4

Shipping
Dimensions
(HWD/in)

14.25 x 10 x 18.5

Shipping
Dimensions
(HWD/cm)

36.2 x 25.4 x 47

Unit weight (lbs)

28.7

Unit weight (kg)

12.92

Unit Dimensions
(HWD/in)

10 x 6.75 x 13.25

Unit Dimensions
(HWD/cm)

25.4 x 17.1 x 33.7

Material of
construction

Steel

Form factors
supported

Tower

Cooling method

Fan

Battery Access

Supports battery access and hot-swap replacement without powering connected equipment off

ENVIRONMENTAL

Relative Humidity

0 to 95%, non-condensing

Storage Temperature

+5 to +122 degrees Fahrenheit/-15 to +50 degrees Celsius

Reviews: