UPS Shipping dimensions (height x
width x depth / inches)

12.7 x 23.6 x 29.1

UPS Shipping dimensions (height x
width x depth / cm)

32.3 x 59.9 x 73.9

Shipping weight (lbs)

157

Shipping weight (kg)

71.1

Cooling method

Fans

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full load)

1767

AC economy mode BTU / hr. (full
load)

765

Battery mode BTU / hr. (full load)

1784

AC mode efficiency rating (100%
load)

90%

AC economy mode efficiency rating
(100% load)

96%

Operating Elevation (ft.)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Operating Elevation (m)

0-3000 m

COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port description

Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports

PowerAlert software

Included

Communications cable

USB, DB9 serial and EPO cables included

WatchDog compatibility

Yes

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Transfer time (economy mode)

8 ms. typical power failure response in optional economy mode

Low voltage transfer to battery
power (setpoint)

156V (full load) / 100V (50% load or less, derates linearly)

High voltage transfer to battery
power (setpoint)

280V (full load) / 300V (90% load or less)

5 / 7 

 

Summary of Contents for SmartOnline SU6000RT4UHVHW

Page 1: ...6 economy mode setting that can significantly reduce a facility s energy costs by minimizing heat output reducing cooling requirements and consuming less electricity An LCD display with LED indicators enables IT personnel to operating modes and conditions The LCD LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various cond...

Page 2: ...trical impulses and other hard to solve power problems not addressed by other UPS types High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs Network grade AC surge and noise suppression Supports detailed monitoring of equipment load levels self test data and utility power conditions via built in RS 232 USB and optional SNMP card slot interfaces UP...

Page 3: ... 10 Output voltage regulation Battery mode 2 Built in UPS output receptacles Hardwire Output receptacle details Hardwire input and output connections are mounted on a detachable PDU backplate with bypass switch to enable hot swappable power module replacement Output AC waveform AC mode Pure Sine wave Output AC waveform battery mode Pure Sine wave INPUT Rated input current at maximum load 31 9A 200...

Page 4: ...itional information and control options Alarms Unique audible alarms for all major UPS environmental and power conditions see manual Alarm cancel operation Alarm cancel switch Switches Includes main power off on switch plus 2 switches to set and execute scrollable LCD functions A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance w...

Page 5: ...0 ft Audible Noise 60 dBA at front side 1 meter Operating Elevation m 0 3000 m COMMUNICATIONS Communications interface USB HID enabled DB9 Serial EPO emergency power off Slot for SNMP Web interface Network monitoring port description Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards RELAYIOMINI installation requires removal of panel containing USB ports P...

Page 6: ...S System 1 2POSTRMKITHD Enables 2 Post Rackmount Installation of 3U and Larger UPS Transformer and Battery Pack Components 1 2 9USTAND Enables Tower Placement of Rackmount UPS Systems 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 ENVIROSENSE Monitors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 RELAYIOCARD Programmable Relay I O ...

Page 7: ...Specifications are subject to change without notice Photos may differ slightly from final products 7 7 ...

Reviews: