INPUT
Rated input current
(at maximum load)
30A
Nominal Input
Voltage(s)
Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS input
connection type
Hardwire
UPS input
connection
description
3 wire single phase input (L1, L2, G); optional, country-specific SUPDM11 backplate adds 2 L6-30R outlets and
L6-30P input cord
Input circuit breaker
40A double-pole
Recommended
Electrical Service
30A 208/220/230/240V
BATTERY
Full load runtime
(minutes)
8 min. (4200w)
Half load runtime
(minutes)
20 min. (2100w)
Expandable battery
runtime
Includes one non-expandable BP240V7RT3U (limit 1) external battery pack. No additional BP240V7RT3U external
battery packs can be connected to the host UPS, beyond the one included with the
SU6000RT3UHV
UPS bundle. All
additional battery packs connected beyond the included BP240V7RT3U, must be
BP240V10RT3U
,
BP240V557C-1PH
,
BP240V787C-1PH
,
BP240V1037C-1PH
or
BP240V1407C-1PH
External battery
pack compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
Less than 6 hours from 10% to 80%
Battery
replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Online, double-conversion power conditioning
Overvoltage
correction
2% output voltage regulation during overvoltages to 276
Undervoltage
correction
2% output voltage regulation during undervoltages to 156
LEDS ALARMS & SWITCHES
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Front panel LCD
display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Alarms
Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel
operation
Alarm cancel switch