any number of additional servers over IP
Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge
current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control
Built-in Emergency Power Off (EPO) interface with cable
Includes 17 built-in output receptacles (3 L6-30R w/one L6-30R used for transformer connection, 2 L6-20R, 12 NEMA 5-15/20R)
L6-30P input plug-in connection
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical
conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures, optional 2POSTRMKITWM supports 2 post
rackmount installation
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
5000
Output kVA capacity
(kVA)
5
Output Watt Capacity
(watts)
3500
Output kW capacity
3.5
Output power factor
0.7
Crest Factor
3:1
Nominal Output
Voltage(s) Supported
120V; 208V
Frequency compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
12 5-15/20R outlet(s); 2 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit breaker
20A breakers (x4) on transformer module protect 3 5-15/20R outlets each, 20A breaker on power module protects
L6-20R outlets, L6-30R outlets are unbreakered
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current (at
maximum load)
24A (208V), 21A (240V)