background image

Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time

Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs

Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other

UPS types

Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 110/120V (+/-2%) values

Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)

Expandable battery runtime with optional BP72V15-2U (limit 1) and BP72V28RT-3U (no limit) external battery packs

Some external battery configurations require the use of Tripp Lite's 

External Battery Configuration Software

 (see manual)

Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches

Ships with all mounting accessories for 4 post rackmount installation

Optional 2POSTRMKITWM enables 2 post rackmount installation (not wallmount compatible)

Optional 2-9USTAND accessory enables small-footprint upright tower placement

Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions

Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot

HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus

any number of additional servers over IP

UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,

battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS

nominal voltage adjustment and UPS line to battery power voltage setpoints

Built-in Emergency Power Off (EPO) interface with cable

NEMA L5-30P input plug; NEMA 5-15/20R & L5-30R output receptacles

Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each

bank has four outlets)

Front panel LEDs offer current monitoring and battery charge level information

UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required

Single line TEL/DSL or network ethernet line surge suppression

$250,000 

Ultimate Lifetime Insurance

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

3000

Output kVA capacity
(kVA)

3

Output Watt Capacity
(watts)

2400

Output kW capacity

2.4

Output power factor

0.8

Crest Factor

3:1

Nominal Output
Voltage(s) Supported

110V; 120V

Nominal Voltage
details

120V default

Frequency
compatibility

50 / 60 Hz

Frequency
compatibility details

Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start

Output voltage
regulation (line mode)

+/- 2%

Summary of Contents for SmartOnline SU3000RTXL3U

Page 1: ...terfaces support simultaneous communications via USB port DB9 serial port and SNMPWEBCARD slot Built in DB9 port offers both enhanced RS 232 enabled monitoring data plus contact closure monitoring ability HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Supports simultaneous detailed monitoring of equipment load level...

Page 2: ...ilt in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown monitoring and control via local connected servers plus any number of additional servers over IP UPS interface supports on battery low battery power restored AC voltage DC voltage output current monitoring battery charge current battery capacity A...

Page 3: ... maximum load 24A Nominal Input Voltage s Supported 110V AC 120V AC UPS input connection type L5 30P Input circuit breaker 40A UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 30A 120V BATTERY Full load runtime minutes 5 min 2400w Half load runtime minutes 14 min 1200w Expandable battery runtime Supports extended runtime with optional external battery packs Exte...

Page 4: ...ow battery overload UPS fault and remote shutdown conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch Switches 2 switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 510 UPS AC suppression response time Instantaneous UPS Dataline suppression 1 line TEL DSL 1 in 1 out 10 100Base T E...

Page 5: ...elsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 1112 7 AC economy mode BTU hr full load 520 9 Battery mode BTU hr full load 1219 3 AC economy mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB HID enabled DB9 Serial Contact closure EPO emergency power off Slot for SNMP Web interface Network monitoring port description Supports detailed monitorin...

Page 6: ...ractive and Online Tower or Rack models 2200 3000VA or less 1 External Battery Packs BP72V15 2U BP72V15 2U External Battery Pack for UPS System 1 External Battery Packs BP72V28RT 3U BP72V28RT 3U External Battery Pack for UPS System 1 Power Cables P043 002 2 ft 10AWG Heavy Duty Power Cord with 20 AMP Breaker NEMA L5 30P to NEMA L5 20R 1 Power Distribution P044 06I 6 inch 12AWG Heavy Duty Power Adap...

Page 7: ...ors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SNMP Accessories SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 Tower Stands 2 9USTAND Enables Tower Placement of Rackmount UPS Systems 1 UPS Accessories MODBUSCARD For remote monitoring and control via MODBUS protocol 1 UPS Accessories RELAYIOCARD Programmable Relay I O Card 1 More i...