background image

Network
monitoring port
description

Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications

PowerAlert
software

Included

Communications
cable

USB and DB9 cabling included

WatchDog
compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

Zero (0 milliseconds) in double-conversion mode; 4 milliseconds economy mode

Low voltage
transfer to battery
power (setpoint)

100V at full load (90V full load at 100V nominal setting); 70V at 70% load; 55V at 33% load

High voltage
transfer to battery
power (setpoint)

150

SPECIAL FEATURES

Cold Start (startup
in battery mode
during a power
failure)

Cold-start operation supported

High availability
UPS features

Automatic inverter bypass; Hot swappable batteries

Green & high
efficiency features

High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of
Hazardous Substances)

WARRANTY

Product Warranty
Period (Worldwide)

2-year limited warranty

Connected
Equipment
Insurance (U.S.,
Canada & Puerto
Rico)

$250,000 

Ultimate Lifetime Insurance

Related Items

Optional Products

Related Model

Description

Qty.

WEXT3-500-1500

3-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack
models, 1500VA or less 

1

WEXT5-500-1500

5-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack
models, 1500VA or less 

1

BP48V24-2U

External Battery Pack for UPS System 

1

BP48V60RT-3U

External Battery Pack and Cable. 3U, Expandable, Blue 2-Point Connector 

1

SNMPWEBCARD

For remote monitoring and control via SNMP, Web or Telnet 

1

Summary of Contents for SmartOnline SU1500RTXLCD2U

Page 1: ...bility HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Includes PowerAlert monitoring software and complete cabling Em...

Page 2: ...gs are reduced for some nominal voltage settings 127 120V 1350 watts 115V 1215 watts 110V 1148 watts 100V 1080 watts FREQUENCY REGULATION CONVERSION MODE Maximum output ratings are reduced in frequenc...

Page 3: ...ed Electrical Service 15A 120V BATTERY Full load runtime minutes 4 2 min 1350w Half load runtime minutes 14 min 675w Expandable battery runtime Extended runtime supported via optional external battery...

Page 4: ...ion and a variety of additional options Alarms Audible alarm indicates UPS startup power failure low battery overload UPS fault and remote shutdown conditions Alarm cancel operation Power fail alarm c...

Page 5: ...ethod Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degre...

Page 6: ...er bypass Hot swappable batteries Green high efficiency features High efficiency economy mode operation Individually controllable load banks Schedulable daily hours of economy mode operation CERTIFICA...

Page 7: ...outlets 2 NEMA 5 15P inputs 1 PDUMNV15 Single Phase Monitored PDU 15A 120V 0U Vertical Rackmount NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Single Phase Switched PDU 15A 120V 0U Vertical Ra...