Battery recharge rate
(included batteries)
Less than 4.5 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC24-SLT
Battery Access
Supports battery access and hot-swap replacement without powering connected equipment off
VOLTAGE REGULATION
Voltage regulation
description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120, 110, 100V nominal
output, without using battery power, during brownouts 95V (120V), 87V (110V), 83V (100V)
Overvoltage correction
Input voltages between 127 and 145V (120V), 116 and 133 (110V), 111 and 121 (100V) are reduced by 12%
Undervoltage
correction
Voltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)
LEDS ALARMS & SWITCHES
LED Indicators
9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for
load and battery charge level
Alarms
Audible alarm warns of power failure condition
Switches
Includes two pushbutton switches for on/off power control and self-test/ alarm cancel functions. Also includes two
dipswitch controls for setting the nominal voltage
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
570 joules
EMI / RFI AC noise
suppression
Yes
AC suppression
response time
Instantaneous
Dataline suppression
Includes 8-wire RJ45 jack; pins 1, 2, 3 and 6 provide 10baseT Ethernet line surge suppression with 7.5V clamping;
pins 4 and 5 provide single-line tel/DSL line surge suppression starting at 260V
PHYSICAL
Installation form
factors supported with
included accessories
Tower
Primary form factor
Tower
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)
10.1 x 6.7 x 13.8
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)
25.7 x 17 x 35.1
UPS / Power Module
weight (lbs)
33.9
UPS / Power Module
weight (kg)
15.4
UPS Shipping
dimensions (height x
width x depth / inches)
13 x 10 x 23.8