door sensors
DHCP/Manual configuration support
10/100 Mbps auto-sensing
Real-time clock backup maintains the time of day and date even if the PDU is unpowered
Tiered access privileges allow an administrator and a guest to login via web browser
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications
TAA Compliant Version Available - Order Tripp Lite PDUMVR20NETAA
Specifications
OVERVIEW
PDU Type
Switched
OUTPUT
Output Capacity Details
1.9kW (120V input), 2.0kW (127V input), 1.6kW (100V input); 20A maximum (Agency de-rated to 16A continuous)
Frequency compatibility
50 / 60 Hz
Output nominal voltage
100-127V nominal, single phase
Outlet quantity / type
24 x 5-15/20R
Outlet Type
NEMA 5-15R, NEMA 5-20R
Customized load management
receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage
100; 120; 127
Maximum Input Amps (A)
20
Maximum Input Amps (A) Details
Agency de-rated to 16A continuous
PDU Plug Type
NEMA 5-20P; NEMA L5-20P
Input cord length (ft.)
10
Input cord length (m)
3
Phase
Single-Phase
LEDS ALARMS & SWITCHES
Front panel LCD display
LCD display reports load level for load bank 1 (upper 12 outlets), bank 2 (lower 12 outlets), bank 1 & 2 combined
(all 24 outlets) or each individual outlet to the nearest amp
2 / 4