Real-time clock backup maintains the time of day and date even if the PDU is not powered on
Tiered access privileges allow an administrator and a guest to login via web browser
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP
protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets
Toolless mounting supported in button-mount compatible racks
Included PDUMVROTATEBRKT enables space saving toolless installation in button-mount compatible racks with PDU outlets facing the
rear
Specifications
OVERVIEW
Model Type
Switched
PDU Type
Switched
OUTPUT
Frequency
compatibility
50 / 60 Hz
Output nominal
voltage
120V
Overload protection
Outlets are arranged in two separately breakered 20A banks. 12 upper outlets are protected by the upper circuit
breaker; 12 lower outlets are protected by the lower circuit breaker
Outlet quantity / type
24 x 5-15/20R
Outlet Type
NEMA 5-15R, NEMA 5-20R
Customized load
management
receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage
100; 120; 127
Maximum Input
Amps (A)
30
Maximum Input
Amps (A) Details
Agency de-rated to 24A continuous
PDU Plug Type
NEMA L5-30P
Input cord length (ft.)
10
Input cord length (m)
3
Voltage
compatibility (VAC)
120
Phase
Single-Phase
LEDS ALARMS & SWITCHES
Switches
Pushbutton switch near the current display toggles the display to show load bank 1 power consumption, load bank 2
power consumption, or load banks 1 and 2 combined power consumption
Front panel LEDs
24 power availability LEDs confirm power off/on status for each built-in outlet. Two additional LEDs with toggle button
identify which bank the visual current meter is reporting (load bank 1, load bank 2, or load banks 1 and 2 combined)
PHYSICAL