background image

INPUT

Recommended Electrical Service

20A 120V

Maximum Input Amps

20

Maximum Input Amps Details

Agency de-rated to 16A continuous

PDU Plug Type

NEMA 5-20P; NEMA L5-20P

Input Phase

Single-Phase

Input Cord Length (ft.)

10

Input Cord Length (m)

3.05

OUTPUT

Output Capacity Details

2.03kW (127V), 1.92kW (120V), 1.6kW (100V) / 20A total capacity (Agency de-rated to 16A); 16A max per outlet

Frequency Compatibility

50 / 60 Hz

Output Receptacles

(24) 5-15/20R

Output Nominal Voltage

100; 120; 127

Customized Load Management
Receptacles

Each outlet is individually controllable via remote interface

USER INTERFACE, ALERTS & CONTROLS

Front Panel LCD Display

Digital meter reports PDU output current in amps

Front Panel LEDs

24 power availability LEDs confirm power off/on status for each built-in outlet

Switches

Recessed reset switch for interface reboot and factory reset

SURGE / NOISE SUPPRESSION

Automatic Shut-Off

No

PHYSICAL

Form Factors Supported

0U vertical rackmount; includes rackmount brackets. Supports toolless mounting in button-mount compatible racks

PDU Form Factor

Vertical (0U)

Shipping Dimensions (hwd / cm)

10.16 x 15.24 x 184.15

Shipping Dimensions (hwd / in.)

4.00 x 6.00 x 72.50

Shipping Weight (kg)

7.03

Shipping Weight (lbs.)

15.50

Unit Dimensions (hwd / in.)

70 x 2.19 x 2.65

Unit Dimensions (hwd / cm)

178 x 5.6 x 6.7

Unit Weight (lbs.)

10

Unit Weight (kg)

4.54

2 / 3