DHCP/Manual configuration support
10/100 Mbps auto-sensing
Real-time clock backup maintains the time of day and date even if the PDU is unpowered
Tiered access privileges allow an administrator and a guest to login via web browser
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications (set of 2 9mm
buttons pre-installed, 2 9mm and 4 6mm spare buttons included)
Nut-and-bolt mounting support for other racks
TAA Compliant Version Available - Order Tripp Lite PDU3VSR10L13TAA
Specifications
OVERVIEW
PDU Type
Switched
OUTPUT
Output Capacity Details
8.6kVA total; 13.9A per bank (balanced)
Frequency compatibility
60 Hz
Output nominal voltage
208V single phase
Overload protection
3 20A double-pole circuit breakers (1 per output phase)
Outlet quantity / type
24 total - 21 C13 (7 per phase), 3 C19 (1 per phase)
Outlet Type
IEC-C13, IEC-C19
Customized load management
receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage
208
Maximum Input Amps (A)
24
PDU Plug Type
NEMA L15-30P
Input cord length (ft.)
10
Input cord length (m)
3.05
Phase
3-Phase
LEDS ALARMS & SWITCHES
Switches
Pushbutton scroll switch enables local power consumption display of each phase or outlet separately, display rotate
and display IP address functions