4
1. Overview and Features
LED and Alarm Indicator
LED 1 LED 2 LED 3 LED 4
LED 5
LED 6
LED 7
LED 8
Alarm
AC Normal
Off
On/
Flashing
Off
Off
10.8V~11.5V 11.5 ~ 12.5V 12.5 ~ 13.5V >13.5V
Off
DC Mode
On
Off
Off
Off
10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
Off
Battery Low
(DC Mode)
On
Off
Off
On
10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
1 beep
@ 5 sec for
3 min.
Low Battery
Cutoff (LBCO)
Off
Off
Off
On
Off
Off
Off
Off
1 beep @
shutdown
Battery High
(AC Mode)
On
Off
Off
Flashing 10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
1 beep
@ 0.5sec
Overload—
110%-129%
(DC Mode)
On
Off
On
Off
10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
1 beep
@ 0.5 sec
Overload—
130%-149%
(DC Mode)
On
Off
On
Off
10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
On
(Constant)
Overload—
>150%
(DC Mode)
On
Off
On
Off
10.2 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.0V >13.0V
On
(Constant)
AC Bypass
Power Off
Off
Off
Off
Off
10.8 ~ 11.5V 11.5 ~ 12.5V 12.5 ~ 13.5V >13.5V
Off
1.2.2 Power ON/OFF Button
The Power ON/OFF button is located in the left of the panel. Press to power the Inverter/Charger ON or OFF. When the button is
pressed, the alarm will beep.
Note: When connected to batteries, the Inverter/Charger will start up even if not connected to AC power. Defaults to 60Hz.
Note: Unit is in BYPASS mode as soon as power is applied to the input.
Power On:
Press the Power ON/OFF button for 3 seconds until the alarm beeps and the INVERTER MODE light illuminates.
Power Off:
Press the Power ON/OFF button for 3 seconds. The alarm will beep when the shutdown process is completed.
1.2.3 DC Mode Inverter (LED 1)
This LED illuminates to indicate that the system is working in inverter mode (supplying power from battery).
1.2.4 AC Mode Charger (LED 2)
The LED flashes during the charging process and remains illuminated once the battery is full charged.
1.2.5 Inverter Condition (LED 3)
When the inverter temperature exceeds the default setting, this LED will flash and the inverter will shut down automatically.
After the temperature returns to normal, depress the Power ON/OFF button to restart.
When the unit is overloaded in DC mode, LEDs 1, 3 and the audible alarm indicate inverter status as follows:
Load Capacity (DC Mode)
LED1
LED 3
Alarm
INVERTER STATUS
110%-129%
On
On
1 beep/0.5sec Shutdown after 60 seconds.
130%-149%
On
On
On (Constant)
Shutdown after 10 seconds.
>150%
On
On
On (Constant)
Shutdown after 1 second.
1.2.6 Battery Limits (LED 4)
Battery High:
In AC mode, LED 4 will flash.
Battery Low:
LED 4 will illuminate and the alarm will beep once every five seconds for three minutes. If the battery voltage
drops below the cutoff voltage (LBCO), then the inverter will shut down all LEDs except LED4, and will turn off.