7
3. Features
3
ATS Source A and Source B Input:
The cords are
permanently attached to the ATS and have L15-30P or L21-
30P plugs.
4
Digital Display:
Shows source status, measured values, display
modes and other information. See the
Digital Display
section
for detailed explanations of the indicators and displays.
5
SNMP Reset Button:
Press the reset button for 3 seconds to
reboot the ATS network card. Rebooting the network card will
not erase network settings or interrupt AC power. The reset
button is recessed. Use a paper clip or other suitable object to
press it.
6
Network Interface:
Use the RJ-45 jack to connect the ATS to the network
with a standard Ethernet patch cable. The Status LED
A
and Link LED
B
indicate operating conditions as shown in the table below. These ports are
not compatible with PoE (Power Over Ethernet) applications.
Network Operating Conditions
A
Status LED Color
B
Link LED Color
Off
Card Not Initialized
Off
No Network Connection
Steady Green
Card Initialized and Operational
Flashing Amber
100 Mbps Network Connection
Flashing Amber
Error - Card Not Initialized
Flashing Green
10 Mbps Network Connection
7
DB9 Configuration Port:
Use this port to provide direct terminal connection to a computer
with a terminal emulation program. A serial cable is included with the ATS. If you need to
order a replacement cable, contact Tripp Lite Customer Support at www.tripplite.com/support.
8
IEC-320-C13 Convenience Outlet:
This outlet receives power from phase L1-L2, but is not
controllable. It contributes to the total L1-L2 load.
9
IEC-320-C13 Convenience Outlet Circuit Breakers:
There are two thermal breakers to
protect each side of the convenience outlet.
10
Circuit Breaker:
Each single phase output load has its own magnetic breaker. If the
connected equipment load exceeds the maximum load rating for that phase, the circuit
breaker will trip. Disconnect excess equipment before resetting the breaker(s).
11
Chassis Ground Screw:
Use this to connect equipment that requires a chassis ground.
12
ATS Mating Receptacle:
This receptacle only accepts the 8-position connector on the power
strip input power cord.
A
B
L15-30P
L21-30P
15-05-226-933363.indb 7