Specifications 

 

Function

 

Range

 

Resolution

 

Accuracy ±(% of 
digits)

 

AC True RMS 
Current 

60.00A 

10mA 

±2.0% of rdg ± 8 digits 

600.0A 

100mA 

±2.5% of rdg ± 8 digits 

Over rang protection: Maximum input 600A; 
Accuracy specified from 5% to 100% of the measuring range; 
Frequency Response:50Hz to 60Hz True RMS; 
Inrush current Maximum Input: 600A;Inrush current 

Sensitivity: >2A. 

DC Current 
Max:600A 

60.00A 

10mA 

±2.0% of rdg ± 8 digits 

600.0A 

100mA 

±2.5% of rdg ± 8 digits 

AC True RMS 
Voltage (with 
VFD) 

6.000V 

1mV 

±1.2% of rdg ± 5 digits 

60.00V 

10mV 

600.0V 

100mV 

1000V 

1V 

±1.5% of rdg ± 5 digits 

Variable frequency drive test AC voltage rang: 100V-600V. 
AC voltage bandwidth: 50 to 1000Hz(Sine); 50/60(All wave). 
Accuracy specified from 5% to 100%of the measuring range. 
Maximum Input: 1000V ac rms. PEAK Maximum Input:1000V. 
DC Voltage 
Maximum Input: 
1000V dc 

6.000V 

1mV 

±0.9% of rdg ± 3 digits 

60.00V 

10mV 

±1.0% of rdg ± 3 digits 

600.0V 

100mV 

1000V 

1V 

±1.2% of rdg ± 3 digits 

Resistance 

600.0Ω 

0.1Ω 

±1% of rdg ± 4 digits 

6.000kΩ 

1Ω 

±1.5% of rdg ± 2 digits 

60.00kΩ 

10Ω 

600.0kΩ 

100Ω 

6.000MΩ 

1kΩ 

±2.0% of rdg ± 5 digits 

60.00MΩ 

10kΩ 

±3% of rdg ± 8 digits 

Input Protection: 300V dc or 300V ac rms. 

Summary of Contents for CM650

Page 1: ...rchase of the Triplett CM650 600A True RMS AC DC Clamp meter The CM650 True RMS AC DC Clamp meter features AC DC Current measurements up to 600A Variable Frequency Drive VFD Voltage Measurements Inrush Current Mode Temperature Measurements Non contact AC voltage detection Auto Power OFF ...

Page 2: ... for longer than 60 days CAUTIONS Improper use of this meter can cause damage shock injury or death Read and understand this user manual before operating the meter Always remove the test leads before replacing the battery The meter itself for any damage before operating the meter Repair or replace any damage before use Use great care when making measurements if the voltages are greater than 25VAC ...

Page 3: ... NCV Non Contact Voltage Indicator LED 4 Clamp Trigger 5 Rotary Function Switch 6 LCD Display 7 Data HOLD Flashlight Button 8 REL Backlight Button 9 Range Button 10 MODE and VFD Button 11 PEAK and INRUSH Button 12 Flashlight 13 Battery Cover 14 COM Input Jack 15 Positive Input Jack ...

Page 4: ...attery 6 Auto Range Mode 7 INRUSH Current Mode 8 Display Hold 9 MAX MIN Mode 10 Variable Frequency Drive VFD Voltage Value 11 Diode Test 12 Continuity Test 13 Auto Power Off APO 14 Faranheit and Celcius Units Temperature 15 Units of Measure Prefixes 16 Hertz Frequency 17 Percent Duty Cycle 18 Measurement Display Digits ...

Page 5: ... then move to the lower ranges if necessary 2 Press the REL button to zero the meter display 3 Use rotary function switch to select 60A AC DC or 600A AC DC range 4 Use MODE Button to select AC or DC 5 Select AC current Test press the INRUSH PEAK Button to turn Inrush current test the LCD will display 6 6 Press the trigger to open jaw Enclose only one conductor For optimum results center the conduc...

Page 6: ...ct the test leads in parallel to the circuit under test 4 Read the voltage measurement on the LCD display Resistance Measurements 1 Insert the black test lead into the COM input jack and the red test lead into the Positive input jacks 2 Set the function switch to the ΩCAP position 3 Touch the test probe tips across the circuit or component under test 4 Read the resistance on the LCD display Contin...

Page 7: ...nction switch to the VAC Hz Position 2 Press MODE Button to select the Frequency Hz or Duty Cycle 3 Touch the test probe tips across the part under test 4 Read the value on the display 5 The display will indicate the proper decimal point and value Temperature Measurements 1 Set the function switch to the TEMP position 2 Insert the Temperature Probe into the negative COM and Positive jacks observin...

Page 8: ...ading displays OL the diode is good If both readings display OL the device is open If both readings are very small or 0 the device is shorted Non Contact Voltage NCV Measurements WARNING Risk of Electrocution always test the Voltage Detector on a known live circuit to verify proper operation before use 1 Touch the probe tip to the hot conductor or insert into the hot side of the electrical outlet ...

Page 9: ...lly in dimly lit areas Press the Hold Flashlight Button to turn the Flashlight on Press again to turn the Flashlight off Range Button Press the RANGE Button to activate the manual mode and to disable the Autorange function The symbol AUTO disappears from the upper left part of the display In manual mode press the RANGE Button to change measuring range the relevant decimal point will change its pos...

Page 10: ... measured value Press the REL Backlight Button to zero the display will appear in the display To exit this mode press the REL Backlight Button again and will disappear in the display DC voltage measurement mode Press the REL Backlight Button to zero the display Press and hold the the REL Backlight Button to turn the Backlight on Press and hold again to turn the Backlight off Auto Power OFF APO In ...

Page 11: ...ent do not use abrasives or solvents If the meter is not to be used for 60 days or more remove the battery and store it separately Battery Replacement 1 Remove the Phillips head screw that secures the rear battery door 2 Open the battery compartment 3 Replace the 1 5V x 3 AAA batteries 4 Secure the battery compartment Type K Temperature Probe Replacement Note To use a Type K thermocouple probe tha...

Page 12: ...tage with VFD 6 000V 1mV 1 2 of rdg 5 digits 60 00V 10mV 600 0V 100mV 1000V 1V 1 5 of rdg 5 digits Variable frequency drive test AC voltage rang 100V 600V AC voltage bandwidth 50 to 1000Hz Sine 50 60 All wave Accuracy specified from 5 to 100 of the measuring range Maximum Input 1000V ac rms PEAK Maximum Input 1000V DC Voltage Maximum Input 1000V dc 6 000V 1mV 0 9 of rdg 3 digits 60 00V 10mV 1 0 of...

Page 13: ...ts Input Protection 1000V AC rms Sensitivity 15V AC rms Frequency AC Current 45Hz to 1kHz 1 0 of rdg 5 digits Sensitivity 20A Duty Cycle 20 0 80 0 0 1 1 2 of rdg 10 digits Temperature 20 to 1000 C 0 1 1 C 3 of rdg 3 C 4 to 1832 F 0 1 1 F 3 of rdg 5 F Sensor Type K Thermocouple Input Protection 300V dc or 300V ac rms Function Testing Condition Reading Diode Forward DCA is approx 1mA open circuit Vo...

Page 14: ...splay 3 readings per second nominal Type K thermocouple 10MΩ VDC and VAC True rms AAC and VAC 2KHz 5 to 40 C 41 to 104 F 20 to 60 C 4 to 140 F Max 80 up to 31 C 87 F decreasing linearly to 50 at 40 C 104 F 80 7000ft 2000meters maximum 3 x 1 5V AAA Batteries 30h Backlight ON 100h Backlight OFF After approx 15 minutes For indoor use and in accordance with the requirements for double insulation to CA...

Page 15: ... date of purchase This warranty does not apply to any of our products which have been repaired or altered by unauthorized persons in any way or purchased from unauthorized distributors so as in our sole judgment to injure their stability or reliability or which have been subject to misuse abuse misapplication negligence accident or which have had the serial numbers altered defaced or removed Acces...