Trion Heremidifier Dual Pneumatic Manual Download Page 12

Dual Pneumatic

I n s t a l l a t i o n ,   O p e r a t i o n   &   S e r v i c e   M a n u a l

12

www.trioniaq.com

Each Dual Pneumatic Atomizing System is custom designed 

for each application to maintain the level of relative humidity 

desired under the conditions to be maintained with the 

equipment as it exists in the area at the time.  If ANY 

conditions change, the demand load for humidification can 

be affected.

Once the system is installed, checked out, and started in 

accordance with the instructions contained in this manual, 

operation is completely automatic to maintain the level 

of relative humidity.  With air and water supplied to the 

equipment, the system cycles ON and OFF as needed.

Set the desired level of RH on the control humidistat, 10% 

more on the safety humidistat, and you can walk away and 

forget it.

If there is a POWER FAILURE, the system automatically 

shuts off.

If there is an AIR COMPRESSOR FAILURE, the system 

automatically shuts off.

If there is a FAILURE OF THE WATER SUPPLY, the heads 

will blow air.

If the water supply PRESSURE is lost or reduced, the heads 

will “sputter”.

If the CONTROL humidistat fails to shut off the system, the 

SAFETY humidistat will shut off the water to the heads at 10% 

above the desired level of RH.  You cannot over-humidify to 

any greater extent than the 10%.

The atomizing heads operate drip free and are self-cleaning 

and self-purging at the end of every ON cycle.  The system 

is designed to go ON and OFF.  Without this cycling, the 

cleaning and purging action is lost.

The system can be started and stopped by merely operating 

the control humidistat.

All  humidification  equipment  needs  periodic  maintenance.  

The procedure for the Dual Pneumatic System is spelled out 

in that section of this manual.  Otherwise, the operation is 

fool-proof and dependable.

VII.  MAINTENANCE INSTRUCTIONS

The Dual Pneumatic Atomizing System requires little 

maintenance to keep it operating properly.  In hard water 

areas and dusty atmospheres, more frequent attention will 

be required.

NORMAL MAINTENANCE required is as follows.

•  AIR COMPRESSOR:

 Follow the air compressor 

manufacturer’s instructions.

•  ATOMIZING HEADS: 

Clean dust and debris from the 

OUTSIDE of the heads as required to keep the spray 

pattern adequate.  At least ONCE A YEAR, remove the 

atomizer nozzles (AH-941-X-X).  Clean these nozzles in 

a weak acid solution.  Do NOT use a wire or other object 

that will score the nozzle or its orifice.

•  AIR & WATER LINES: 

Blow out all supply lines at least 

ONCE A YEAR using the procedures covered under 

start-up of the system in this manual.  Check all joists 

and valves for leaks ONCE A YEAR.

•  STRAINERS: 

Strainers on air and water controls (both 

primary regulators and control section regulators) should 

be cleaned ONCE A YEAR and replaced as required.  

Strainer screens (AH-21) in the strainer union assembly 

(AH-17) of each head should be cleaned ONCE A YEAR.  

If air strainers are dirty or oily, it may be necessary to 

install an air dryer or after cooler on the compressor or a 

separator on the air line.

•  HUMIDISTATS: 

Calibration should be checked with a 

dependable psychrometer at least ONCE A YEAR and 

adjusted as needed.

•  HYGROMETERS:

 (RH indicators) Use psychrometer to 

check for accuracy.

•  PRESSURE REGULATORS: 

Air and water (primary 

and control sections) - check operation at least ONCE A 

YEAR to be sure regulation to desired pressures is being 

maintained properly.

•  SOLENOID VALVES:

 Air and water (control sections) - 

check operation at least ONCE A YEAR to be sure their 

operation is proper and valves do not leak.

After the removal and re-installation of heads and control 

sections, ALWAYS follow the start-up procedure to be sure 

all foreign matter is flushed from the lines and none reaches 

the heads.

Your system will last indefinitely if properly maintained.

VIII. TROUBLESHOOTING

HEAVY SPRAY PATTERN (Droplets too large)

ALL HEADS served by one control section: either this is 

caused by too low a setting on the air pressure regulator of 

the air control section, which calls for slightly increasing the 

air pressure - or too high a setting on the water regulator 

of the water control section, which requires decreasing the 

water setting slightly.

NEVER LET AIR PRESSURE EXCEED WATER PRESSURE.

INDIVIDUAL HEADS: These heads are not getting enough air.

1.  Foreign matter may be clogging the screen (AH-21) in 

the air strainer union (AH-17) of the head.

2.  One or more heads served by the same control section 

may have been IMPROPERLY ADJUSTED by throttling 

the valves at the head assembly.  No valves should ever 

be throttled!

3.  Water nozzle (AH-942-X) orifice may have been enlarged 

due to bent cleaning needle on diaphragm (AH-10).  

Summary of Contents for Heremidifier Dual Pneumatic

Page 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Page 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Page 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Page 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Page 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Page 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Page 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Page 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Page 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Page 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Page 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Page 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Page 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Page 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Page 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Page 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Page 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Page 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Reviews: