Entity
–
Operational Manual
TRINITY
[8]
Operational Details:
The energy based Entity is a versatile meter with all the features needed to
implement for a robust electrical system. It can be configured to suit for the
measurement of energy. There are two types of operational Mode in this unit such as
Programming Mode and Run Mode.
After supplying power (80 to 270 VAC), the unit will display with power receiving
information such
as “---TRINITY ”, CT Ratio, Device Id (Only In the KWh variant)
and then enters into Run Mode by default with the following display.
Programming Mode:
The unit has programmable parameters CT-Primary, CT Secondary and Device Id and
is also easy user interface by pressing three keys such as, , and
Setting CT-Primary:
The CT-Primary is freely programmable from 5 to 5000 A of which 5 to 200 can be
set with the steps of 5 and 200 to 5000 with the steps of 25, and hence the CT
setting falls onto the standard rating of user’s desire. The CT setting thus gives the
true current value for CT operated meter in your electrical installation system.
To set the CT-Primary, proceed the following instructions.
1. In Run Mode display, press
key for about 4 to 5 seconds continuously. The
unit will enter into Programming Mode with the following display.
2.