 Operational Manual 

TRINITY 

[8] 

    

 

 

 
 

 

Operational Details: 

 

The  energy  based  Entity  is  a  versatile  meter  with  all  the  features  needed  to 
implement  for  a  robust  electrical  system.  It  can  be  configured  to  suit  for  the 
measurement of energy. There are two types of operational Mode in this unit such as 
Programming Mode and Run Mode. 

After  supplying  power  (80  to  270  VAC),  the  unit  will  display  with  power  receiving 
information such 

as “---TRINITY ”, CT Ratio, Device Id (Only In the KWh variant) 

and then enters into Run Mode by default with the following display. 
 
 

 

 

 

 

Programming  Mode: 

 

The unit has programmable parameters CT-Primary, CT  Secondary and Device Id and  
is also easy user interface by pressing three keys such as,       ,       and         

 

 
 
Setting  CT-Primary: 

 

The CT-Primary is freely programmable from 5 to 5000 A of which 5 to 200 can be 
set  with  the  steps  of  5  and  200  to  5000  with  the  steps  of  25,  and  hence  the  CT 
setting falls onto the standard rating of user’s desire. The CT setting thus gives the 
true current value for CT operated meter in your electrical installation system. 

 

To set the CT-Primary, proceed the following instructions. 

 

1.  In Run Mode display, press 

 key for about 4 to 5 seconds continuously. The 

unit will enter into Programming Mode with the following display. 

2.   

 

 

 

 

   

          

 

Summary of Contents for ENTITY

Page 1: ...he unit is tested against latest MTE Standard Model PRS 1 3 having basic accuracy of 0 02 traceable upto International Standards derived using appropriate ratio techniques The product Entity is sophisticated electronic equipment and the user is advised to read this User s Manual carefully before attempting to install or operate the equipment Published on 05 03 2019 Document Version 1 1 ...

Page 2: ...rranty What This Warranty Does Not Cover This warranty does not apply to refurbished or reconditioned products This warranty covers only normal use in India This warranty does not cover damage to the Trinity product caused by parts or supplies not manufactured distributed or certified by Trinity This warranty is not transferable This warranty does not cover third party parts components or peripher...

Page 3: ...es Available in This Model 4 Technical Specifications 5 Installation and Commissioning 6 Connection Scheme 7 Operational Details 8 Programming Mode 8 Setting CT Primary 8 Setting CT Secondary 9 Setting Device ID 9 Run Mode 10 Resetting Energies 10 Communication 11 Appendix 11 ...

Page 4: ...n the system Entity is a low cost effective easy user interface and can measure accurate KWh energy that displays on 16X1 LCD The unit supports only for three phase four wire in an electrical installation The Main Features Available in This Model Class 1 0S accuracy as per IS13779 Class 0 5S accuracy also available Compact 96 x 96 x 55 mm enclosure Microcontroller based with true RMS measurement 1...

Page 5: ...ectable Range of Reading 5 5000A Burden 1 0VA Overload Through CT 5A CT 6A RMS Continuous 1A CT 1 2A RMS Continuous Whole Current 120 of Imax continuous Power Supply Wide operating Voltage SMPS 80 VAC 270 VAC 50 60 Hz MEASUR EMENT Energy Total Active Energy KWh Range of Reading 0 to 9999999 9 KWh Accuracy 1 0S as per IS13779 Dimensions Bezel 96 X 96 mm Panel Cutout 92 X 92 mm Depth of installation...

Page 6: ...mage due to sever overvoltage or phase fault in the system 4 Connect the two wires from R phase CT to the terminals marked M1 and L1 such that S1 goes to the terminal marked M1 Connect the two wires coming from the Y phase CT to the terminals marked M2 and L2 such that S1 from the CT goes to terminal marked M2 Connect the two wires coming from B phase CT to the terminals marked M3 and L3 such that...

Page 7: ...TRINITY 7 Entity Operational Manual Connection Scheme Note A B only applicable for Rs 485 Variant ...

Page 8: ...the following display Programming Mode The unit has programmable parameters CT Primary CT Secondary and Device Id and is also easy user interface by pressing three keys such as and Setting CT Primary The CT Primary is freely programmable from 5 to 5000 A of which 5 to 200 can be set with the steps of 5 and 200 to 5000 with the steps of 25 and hence the CT setting falls onto the standard rating of ...

Page 9: ...CT Secondary with following display 2 Press PROG ENTR key again Immediately P starts blinking which indicates that the parameter can now be changed Set the parameter value by pressing UP and DOWN keys untill the desired value is received 3 Press PROG ENTR key to confirm the parameter value Hence the unit will restart and return into Run Mode Setting Device Id The unit also supports RS485 communica...

Page 10: ...alue is received 3 Press PROG ENTR key to confirm the parameter value Hence the unit will restart and return into Run Mode Run Mode In the Run Mode KWh energy calculated by the unit is displayed on a 16X1 LC display such as shown below Resetting Energies The Active Energy KWh can be reset by pressing key and key simultaneously for about 8 seconds Hence the unit will restart and return into Run Mod...

Page 11: ... software ENTITY supports an RS485 port with MODBUS RTU protocol The station ID for every meter is site selectable The data which can be read using MODBUS query 3 Read Holding Registers is provided inan address map with the applicable multiplication factors vide Appendix Communication line parameters 9600 8 N 1 The register map is described below All addresses are in decimal Parameter is Unsigned ...

Page 12: ...nducted to relevant standards and our Specifications Literature O M Manual Traceability tested against latest MTE Standard Model PRS 1 3 having basic accuracy of 0 02 traceable upto International Standards derived using appropriate ratio techniques Result of Test Remarks Test engineer Date ...

Page 13: ...Entity Operational Manual TRINITY 13 ...

Reviews: