31
HPP5500
series
D
I-value reaches at maximum or minimum
limit.
Changes
in
valve
friction.
Changes in setting pressure of actuator.
Perform
auto
calibration.
Check setting pressure of actuator.
7.2 Warning
code
Warning
Code
Description
Action
B
Pv Span – Pv Zero range is below 500.
The angle of feedback lever is too small.
Re-install
the
positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1.
F
Full open/close elapsed time is less
than 1 second.
Actuator size is too small.
Use
variable
orifice.
Use larger actuator.
G
Pv is below 100.
The angle of feedback lever is too large.
Re-install
the
positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1
H
Pv is over 4000.
The angle of feedback lever is too large.
Re-install
the
positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1