For use with the following models:
Wall Speakers:
TR-SPRL, TR-SPWL
Ceiling Speakers:
TR-SPCRL, TR-SPCWL
PRODUCT SPECIFICATIONS
Standard Operating Temperature:
32°F to 120°F (0°C to 49°C)
Humidity Range:
10 to 93% Non-condensing
Nominal Voltage:
25 Volts or 70.7 Volts
Maximum Supervisory Voltage:
50 VDC
Speaker Frequency Range:
400 – 4000 Hz
Power Settings:
¼, ½, 1, 2 Watts
Input terminal wire gauge:
12 to 18 AWG
PRODUCT DIMENSIONS
MOUNTING BOX OPTIONS
WALL PRODUCTS
Length
Width
Depth
SPEAKERS
Wall Speaker
6.520" (165 mm)
5.00" (127 mm)
0.97" (24.6 mm)
SBBSPRL/SBBSPWL (wall), SBBCRL/SBBCWL
(ceiling), 4" x 4" x 2
1
/
8"
or deeper
(When using 12AWG, 14 AWG, or adding extra
wires in the box, a deeper box or extension
ring is recommended.)
CEILING PRODUCTS
Length
Width
Depth
Ceiling Speaker
6.8" (173 mm)
N/A
1.00" (25.4mm)
NOTICE:
This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
These notification appliances offer a wide range of audible and visible
devices for life safety notification. Our line of speakers is designed to be used
at either 25 or 70.7 volts, and operate at any one of four input power levels.
Our speak-ers are suitable for dry and damp environments. With its low
total harmonic distortion, the SPL series offers high fidelity sound output.
Wall and ceiling products may be used interchangeably (wall products may
be used on ceiling and ceiling product may be used on wall).
The speakers, and all power level settings, are listed to ANSI/UL 1480
require-ments for public mode applications.
FIRE ALARM SYSTEM CONSIDERATIONS
All wiring must be installed in compliance with the National Electrical Code
(NEC) and applicable local codes. Triga recommends installing fire
alarm speakers in compliance with NFPA 72, ANSI/UL 1480 and NEC 760.
WIRING AND MOUNTING
All wiring must be installed in compliance with the National Electric Code
and the local codes as well as the authority having jurisdiction. Wiring
must not be of such length or wire size which would cause the notification
appli-ance to operate outside of its published specifications. Improper
connections can prevent the system from alerting occupants in the event of
an emergency.
Wire sizes up to 12 AWG (2.5 mm²) may be used with the mounting plate.
The mounting plate ships with the terminals set for 12 AWG wiring.
Make wire connections by stripping about
3
/
8
" of insulation from the end
of the wire. Then slide the bare end of the wire under the appropriate
clamping plate and tighten the clamping plate screw.
See Figure 1 for wiring terminals and strip guide reference.
1. Connect the speaker. (See Figure 1.)
2. There are two rotary switches on the back of the product. The first switch
is used to select either 25 or 70.7 volts input and the second switch is used to
select the input power of ¼, ½, 1 or 2 watts. (See Figure 2.)
FIGURE 1. WIRING DIAGRAM AND WIRING TERMINALS
(-)
(+)
(-)
(+)
Input from
Amplifier
Output to
Next Device or EOL
A0380-02
Wiring Terminals
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
NOTE: Do not loop electrical wiring
under terminal screws. Wires
connecting the device to the control
panel must be broken at the device
terminal connection in order to
maintain electrical supervision.