PRELIMINARY:
TR-FML/TR-FSL Product Installation Document —
P/N LSL10178-003TR-E:A 02/03/21
All components should be located per the following require-
ments:
•
Installations are to be indoors only, in dry locations,
protected from rain, water, and rapid changes in temperature
that could cause condensation.
•
Equipment must be securely mounted on rigid, permanent
walls.
•
Operating temperature shall not exceed the range of 32° to
120° F (0 to 49° C).
•
Operating humidity not to exceed 93% non-condensing at
90° F (32° C).
•
All sub-assemblies and components are to be located in
compliance with the local, the national codes and the
manufacturer’s recommendations.
•
All installation field wiring shall be in compliance with the
local code, the national code and the manufacturer’s
recommendations.
•
Use the Architects and Engineering Specifications for
detailed information on your Facility’s Configuration.
2.1 TR-FML/TR-FSL Installation
1. Remove the unit from its static-shield bag, observing proper
static protection measures.
2. Visually inspect the unit for damage.
If any components are damaged, notify the shipping carrier
immediately. Report missing components to the Triga
Customer Service.
3. Use the hardware kit provided with the unit.
4. Plug the Fiber Module #1 into P6 of the ECS-NVCM or TR-
NIC circuit as shown in Location 1 in Figure 3 and Figure 4.
5. To connect the Fiber Module # 1 to the ECS-NVCM or TR-
NIC, insert and secure three screws (#4-40 x 1/4” (.635 cm))
as shown in Location 2 in Figure 3 and Figure 4.
6. Plug the Fiber Module #1 into P5 of the ECS-NVCM or TR-
NIC circuit as shown in Location 3 in Figure 3 and Figure 4.
7. To connect the Fiber Module #1 to the ECS-NVCM or TR-
NIC, insert and secure three screws (#4-40 x 1/4” (.635 cm))
as shown in Location 4 in Figure 3 and Figure 4.
NOTE:
FIBER MODULES:TR-FSL AND TR-FML
Install a maximum of two boards per installation. The fiber
modules can be combined.
Figure 3 illustrates the TR-FML/TR-FSL installed to the
TR-NIC.
Figure 3 TR-FML Installation
Figure 4 illustrates the TR-FML/TR-FSL installed to the
ECS-NVCM.
Figure 4 TR-FSL Installation
TR-NIC
TR-FML
TR-FSL
TR-FML
TR-FSL
FIK
-FM
L
FIK
-FS
L
TR-FML
TR-FSL
ECS-NVCM
TR-FML
TR-FSL