WIRING INSTRUCTIONS
Make wiring connections by stripping about
3
/
8
" (10 mm) of insulation from
the wire end. Then, insert the wire into the appropriate terminal and tighten
the screw. Wire the communication line in (+) to terminal 1. Insert both
communication line in (–) and communication line out (–) to terminal 2. Wire
communication line out (+) to terminal 3 (see Figures 3 and 4).
A label is affixed to the base for recording the zone, address, and type of
detector being installed at the base location. This information is useful for set-
ting the detector head address and for verification of the sensor type required
for that location.
Once all detector bases have been wired and mounted, and the loop wiring
has been checked, the detector heads may be installed in the bases.
TAMPER-RESIST FEATURE
NOTE:
Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool.
To activate this feature, break the tab from the detector base as shown in
Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever. (See Figure 5B). This allows the detector to be ro-
tated counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used
again.
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
(–)
(+)
(–)
(+)
3 (+)
2 (–)
2 (–)
1 (+)
2 (–)
1 (+)
3 (+)
2 (–)
(+)
(–)
(–)
(+)
(+)
(–)
(–)
(+)
2 (–)
2 (–)
3 (+)
1 (+)
2 (–)
2 (–)
3 (+)
1 (+)
(+)
(–)
COMMUNICATION LINE
ALL WIRING SHOWN IS SUPERVISED.
A PAIR OF FAULT ISOLATOR BASES WILL
DISCONNECT A GROUP OF DEVICES IF A
SHORT CIRCUIT OCCURS ON THE SIGNALING
LINE CIRCUIT WITHIN THAT GROUP.
GROUPS OF ADDRESSABLE DEVICES ARE
SEPERATED BY FAULT ISOLATOR BASES. ANY
COMBINATION OF COMPATIBLE LISTED DEVICES
MAY BE MIXED WITHIN A GROUP
COMPATIBLE
CONTROL PANEL
GROUP 1
GROUP 2
GROUP 3
C1013-01
FIGURE 4. WIRING DIAGRAM
FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE.
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW.
C1065-00
FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE
SLOT
SLOT
C1082-00