WIRING INSTRUCTIONS

Make wiring connections by stripping about 

3

/

8

" (10 mm) of insulation from 

the wire end. Then, insert the wire into the appropriate terminal and tighten 
the screw. Wire the communication line in (+) to terminal 1. Insert both 
communication line in (–) and communication line out (–) to terminal 2. Wire 
communication line out (+) to terminal 3 (see Figures 3 and 4).
A label is affixed to the base for recording the zone, address, and type of 
detector being installed at the base location. This information is useful for set-
ting the detector head address and for verification of the sensor type required 
for that location.
Once all detector bases have been wired and mounted, and the loop wiring 
has been checked, the detector heads may be installed in the bases.

TAMPER-RESIST FEATURE

NOTE:

 Do not use the tamper-resist feature if the removal tool is to be used.

This detector base includes a tamper-resist feature that prevents its removal 
from the base without the use of a tool. 
To activate this feature, break the tab from the detector base as shown in 
Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been 
activated, insert a small-bladed screwdriver into the slot from the top and 
press down on the lever. (See Figure 5B). This allows the detector to be ro-
tated counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used 
again.

(+)

(–)

(–)
(+)

(–)
(+)

(+)

(–)

(–)
(+)

(–)
(+)

3 (+)

2 (–)

2 (–)

1 (+)

2 (–)

1 (+)

3 (+)
2 (–)

(+)

(–)

(–)
(+)

(+)

(–)

(–)
(+)

2 (–)

2 (–)

3 (+)

1 (+)

2 (–)

2 (–)
3 (+)

1 (+)

(+)

(–)

COMMUNICATION LINE

ALL WIRING SHOWN IS SUPERVISED.

A PAIR OF FAULT ISOLATOR BASES WILL 

DISCONNECT A GROUP OF DEVICES IF A 

SHORT CIRCUIT OCCURS ON THE SIGNALING 

LINE CIRCUIT WITHIN THAT GROUP.

GROUPS OF ADDRESSABLE DEVICES ARE 

SEPERATED BY FAULT ISOLATOR BASES. ANY 

COMBINATION OF COMPATIBLE LISTED DEVICES 

MAY BE MIXED WITHIN A GROUP

COMPATIBLE 

CONTROL PANEL

GROUP 1

GROUP 2

GROUP 3

C1013-01

FIGURE 4. WIRING DIAGRAM

FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE.

USE SMALL-BLADED SCREWDRIVER TO PUSH

PLASTIC LEVER IN DIRECTION OF ARROW.

C1065-00

FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE

SLOT

SLOT

C1082-00

Triga™ is a trademark of TRIGA Life Safety Systems, LLC. 

2

I56-3736TRG-005 

©2021. 2/1/2021