Data sheet 11/20-EM111-1

Emergency lighting units

EM converterLED

The  DELAY and INTERVAL time values must be re-set when the emergency 
system test times are to be scheduled by a DALI control and monitoring 
system.
Note that once the default values have been set to Zero, tests will only be 
conducted following a command from the control system. If the DALI bus is 
disconnected the EM converterLED PRO does not revert to self-testing 
mode.

Note: If the battery is connected the DALI communication is only possible 
after power reset.

Addressing

The EM converterLED PRO includes the EZ easy addressing system which 
allows addressing and identification by using the bi-colour LED. Binary 
address codes given by the LED can be simply converted to the DALI 
addresses 0 to 63. For single handed addressing using this method it is 
necessary to send a broadcast ident command every 3 to 9 seconds. During 
this command the LEDs will be switched off and the indication LED will flash 
the 6 bit binary address preceded by a 3 second start indication period.

Commissioning

After installation of the luminaire and initial connection of the mains supply 
and battery supply to the EM converterLED PRO the unit will commence 
charging the batteries for 20 hours (initial charge). Afterwards the module 
will conduct a commissioning test for the full duration. The 20 hours rechar-
ge occurs also if a new battery is connected or the module exits the rest 
mode condition. The following automatic commissioning duration test is only 
performed when a battery is replaced and fully charged (after 20 hrs) and 
the interval time is not set to zero, otherwise the system is expected to per-
form the testing.

Functional test

The time of day and frequency of the 5 seconds function test can be set by 
the DALI controller. The default setting is a 5 seconds test on a weekly basis.

Duration test

The time of day and frequency of the duration test can be set by the DALI 
controller. The default setting is a duration test conducted every 52 weeks.

For 2 h operation:
The first commissioning duration test has a time of 120 minutes, subse-
quent through life tests are conducted for 90 minutes. When the battery is 
changed or disconnected and re-connected the unit will next conduct a 120 
minute test.

Prolong time

Prolong time can be set by the DALI controller.  This is the delay time bet-
ween return of the mains supply and the end of the emergency operation. 
The default prolong time is set as 0 minutes as specified within the DALI 
standard.
Indicator LED will stay off for the duration of the prolong time.

Rest Mode / Inhibit Mode

Emergency operation is automatically started when the mains supply is 
switched off. If the Rest Mode is activated, the discharging of the battery will 
be minimized by switching off the LED output. If the Inhibit Mode has been 
activated before the mains supply is switched off, Rest Mode will be automa-
tically switched on if the mains supply is switched off within 15 minutes.
Rest Mode and Inhibit Mode can be initiated by the DALI controller. The 
REST command has to be sent after the mains supply has been discon-
nected and whilst the EM converterLED PRO is in emergency operation. 
The INHIBIT command has to be sent while the EM converterLED PRO is 
supplied by mains.
After a mains reset the EM converterLED PRO exits the Rest Mode. Rest 
Mode and Inhibit Mode can both be disabled by sending the RE-LIGHT/
RESET INHIBIT command.

Test switch

An optional test switch can be wired to each EM converterLED.  
This can be used to to:
•  Initiate a 5 seconds function test: 

press 200 ms < T < 1 s

•  Execute function test as long as switch pressed:  press > 1 s
•  Reset selftest timer (adjust local timing): 

press > 10 s

Timer reset functionality

The timer for function and duration test can be set to a particular time of the 
day by either pressing the test switch for longer than 10 seconds or cycling 
the unswitched line supply 5 times within 1 minute. The timer adjustment 
will enable the test start time to be defined manually at time in day when 
the timer was reset. It will also disable the adaptive test algorithm thereby 
forcing the unit to perform the test at the same time rather than it being 
defined by the adaptive algorithm. This function will only work provided the 
interval time is greater than zero (automatic test mode enabled). The delay 
timer value set when the unit was commissioned will be reloaded in order to 
randomise the tests between adjacent units.

BlackBox data recording

Parameters providing information about the application and use are stored 
in the EM converterLED PRO. The parameters stored provide information on 
the mains,  battery, LED output and emergency operation.
The BlackBox can be read out with the masterCONFIGURATOR and  
deviceANALYSER.

DALI Controller

DALI controllers and hardware/software solutions are available from Trido-
nic. Please refer to the Lighting controls section.

Summary of Contents for 89800643

Page 1: ...ayed power switching for the LED Driver Constant power output Two colour status display LED Black Box data recording Interfaces DALI interface for controlled testing and monitoring Near field communication NFC Battery management NiMH LiFePO4 Intelligent charge system Deep discharge protection Polarity reversal protection for battery via polarized connector plug Automatic detection of the connected...

Page 2: ...rgency Mains current in charging operation Rated power in charging operation Initial charge3 Fast recharge3 Trickle charge23 Initial charge3 Fast recharge3 Trickle charge23 EM converterLED PRO 303 MH LiFePO4 250V NiMH 1 h 0 6C 2 5 W 17 mA 20 mA 17 12 mA 2 3 W 2 8 W 2 3 1 6 W 2 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W 3 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W LiFePO4 ...

Page 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Page 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Page 5: ...lure rate of 0 2 per 1000 operating hours Expected life time with LiFePO4 batteries DALI power supply off Type ta 40 C 45 C 50 C 55 C EM converterLED PRO 303 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 304 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 305 MH LiFePO4 250V tc 6...

Page 6: ...Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear LED Module Emergency LED Module LED Module LED control gear max 150 W in operation DALI bus Integrated power supply Battery Neutral Bat P O Lout Lin N DA DA L L N EM ConverterLED PRO Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched...

Page 7: ...ect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4 Direct connection NiMH Connection with extension cable When using an EM converterLED in combination with a NiMH battery order the CONNECTION CABLE NiMH 500mm seperately LiFePO4 Connection with extension cable Battery 300 EM converterLED Battery 500 300 EM converterLED Battery 500 300 EM converterLED Neutr...

Page 8: ...al and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the EMC performance of the luminaire 3 6 Maximum lead length LED 3 m 6 m loop 1 Status indication LED 1 m Batteries 0 8 m 1 Note The...

Page 9: ... converterLED PRO MH LiFePO4 250V 90 130 130 130 180 260 260 260 3 6 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver ...

Page 10: ... battery discharge current tolerance EM converterLED PRO 304 MH LiFePO4 250V Article number 89800644 NiMH battery 4 8 V battery voltage 810 870 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 1 285 1 375 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 305 MH LiFePO4 250V Article number 89800645 NiMH battery 6 0 V b...

Page 11: ...ure Battery failed the duration test or function test Battery is defect or deep discharged Incorrect battery voltage Fast flashing red 0 1 sec on 0 1 sec off Charging failure Incorrect charging current Double pulsing green Inhibit mode Switching into inhibit mode via controller Binary transmission of address via green red LED Address identification During address identification mode Green and red ...

Page 12: ... set by the DALI controller This is the delay time bet ween return of the mains supply and the end of the emergency operation The default prolong time is set as 0 minutes as specified within the DALI standard Indicator LED will stay off for the duration of the prolong time Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is ...

Page 13: ... battery will be charged below 0 9 V The EM converterLED will indicate a battery fault The emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED PRO 1 2 3 h Type EM converterLED PRO 303 MH LiFePO4 250V EM converterLED PRO 304 MH LiFePO4 250V EM converterLED PRO 305 MH LiFePO4 250V Article no 898006...

Page 14: ...ycles per year plus 30 cycles during comissioning Max storage time 12 months at 5 C to 25 C 8 4 Accu LiFePO4 Capacity 1 5 Ah International designation IFpR 19 66 Battery voltage cell 3 2 V Cell type 18650 Case temperature range to ensure 4 years design life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number disch...

Page 15: ...operation The Black Box can be read out with the masterCONFIGURATOR and deviceANALYSER via DALI and NFC In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no battery is not connected1 4 Connect new battery 5 Connect main...

Reviews: