Data sheet 11/20-EM111-1

Emergency lighting units

EM converterLED

Product description

•  Self-contained emergency lighting LED Driver with    

DALI interface and automatic test function

•  For LED modules with a forward voltage of 48 – 250 V
•  For luminaire installation
•  Nominal life-time up to 100,000 h
•  5-year guarantee

Functions

•  Non maintained operation
•  Integrated DALI bus power supply
•  1, 2 or 3 h rated duration selectable with duration link
•  Compatible with most constant current LED Drivers (refer to 

chapter „LED Driver compatibility“)

•  3-pole technology: 2-pole LED module changeover 

and delayed power switching for the LED Driver

•  Constant power output
•  Two-colour status display LED
•  Black Box data recording

Interfaces

•  DALI interface for controlled testing and monitoring
•  Near field communication (NFC)

Battery management

 NiMH/LiFePO4:
•  Intelligent charge system
•  Deep discharge protection
•  Polarity reversal protection for battery via polarized connector 

plug

•  Automatic detection of the connected battery technology  

(NiMH or LiFePO

4

 batteries)

 LiFePO4:
•  Tridonic LiFeGuard ensures safety in use (refer to chapter  

„Safety LiFePO

4

“)

•  Temperature protection

Batteries

•  NiMH or LiFePO

4

 batteries

•  NiMH: 4-year design life / 1-year guarantee

•  LiFePO

4

: 4 – 8 years design life / 3-year guarantee

•  For battery compatibility refer to chapter „Battery selection“

È

Standards

, page 5

Wiring diagrams and installation examples

, page 6

EM converterLED PRO NF MH/LiFePO4 250 V

Powered DALI PRO NFC series

 

Summary of Contents for 89800643

Page 1: ...ayed power switching for the LED Driver Constant power output Two colour status display LED Black Box data recording Interfaces DALI interface for controlled testing and monitoring Near field communication NFC Battery management NiMH LiFePO4 Intelligent charge system Deep discharge protection Polarity reversal protection for battery via polarized connector plug Automatic detection of the connected...

Page 2: ...rgency Mains current in charging operation Rated power in charging operation Initial charge3 Fast recharge3 Trickle charge23 Initial charge3 Fast recharge3 Trickle charge23 EM converterLED PRO 303 MH LiFePO4 250V NiMH 1 h 0 6C 2 5 W 17 mA 20 mA 17 12 mA 2 3 W 2 8 W 2 3 1 6 W 2 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W 3 h 0 6C 2 5 W 24 mA 25 mA 20 12 mA 3 2 W 3 4 W 2 7 1 6 W LiFePO4 ...

Page 3: ...ct description Two colour status display LED Green system OK red fault Plug connection Status indication bi colour LED ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 20...

Page 4: ...g connection for LED Driver Connection Cable NiMH ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc CONNECTION CABLE NiMH 500mm 28002462 10 pc s 200 pc s 0 015 kg Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging...

Page 5: ...lure rate of 0 2 per 1000 operating hours Expected life time with LiFePO4 batteries DALI power supply off Type ta 40 C 45 C 50 C 55 C EM converterLED PRO 303 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 304 MH LiFePO4 250V tc 65 C 70 C 75 C 80 C life time 100 000 h 100 000 h 82 000 h 58 000 h EM converterLED PRO 305 MH LiFePO4 250V tc 6...

Page 6: ...Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched Line in Control gear LED LED Control gear LED Module Emergency LED Module LED Module LED control gear max 150 W in operation DALI bus Integrated power supply Battery Neutral Bat P O Lout Lin N DA DA L L N EM ConverterLED PRO Neutral DALI DALI Un Switched Line Test switch Indicator LED Switched Line out Switched...

Page 7: ...ect operation of terminals Wiring LED module LED Driver supply 3 3 Battery connection LiFePO4 Direct connection NiMH Connection with extension cable When using an EM converterLED in combination with a NiMH battery order the CONNECTION CABLE NiMH 500mm seperately LiFePO4 Connection with extension cable Battery 300 EM converterLED Battery 500 300 EM converterLED Battery 500 300 EM converterLED Neutr...

Page 8: ...al and emergency mode it is essential to follow good practice in the wiring layout Within the luminaire the switched and unswitched 50Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads Through wiring may affect the EMC performance of the luminaire 3 6 Maximum lead length LED 3 m 6 m loop 1 Status indication LED 1 m Batteries 0 8 m 1 Note The...

Page 9: ... converterLED PRO MH LiFePO4 250V 90 130 130 130 180 260 260 260 3 6 A 120 μs 5 Electrical values 5 1 Maximum loading of automatic circuit breakers 5 2 Insulation matrix Mains Switched Live Battery LED Test switch Indicator LED DALI Mains Switched Live Battery LED Test switch Indicator LED DALI Represents basic insulation Represents double or reinforced insulation When using a non SELV LED Driver ...

Page 10: ... battery discharge current tolerance EM converterLED PRO 304 MH LiFePO4 250V Article number 89800644 NiMH battery 4 8 V battery voltage 810 870 mA battery discharge current tolerance LiFePO4 battery 3 2 V battery voltage 1 285 1 375 mA battery discharge current tolerance LED current mA VLED V VLED V LED current mA EM converterLED PRO 305 MH LiFePO4 250V Article number 89800645 NiMH battery 6 0 V b...

Page 11: ...ure Battery failed the duration test or function test Battery is defect or deep discharged Incorrect battery voltage Fast flashing red 0 1 sec on 0 1 sec off Charging failure Incorrect charging current Double pulsing green Inhibit mode Switching into inhibit mode via controller Binary transmission of address via green red LED Address identification During address identification mode Green and red ...

Page 12: ... set by the DALI controller This is the delay time bet ween return of the mains supply and the end of the emergency operation The default prolong time is set as 0 minutes as specified within the DALI standard Indicator LED will stay off for the duration of the prolong time Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is ...

Page 13: ... battery will be charged below 0 9 V The EM converterLED will indicate a battery fault The emergency lighting LED Driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions EM converterLED PRO 1 2 3 h Type EM converterLED PRO 303 MH LiFePO4 250V EM converterLED PRO 304 MH LiFePO4 250V EM converterLED PRO 305 MH LiFePO4 250V Article no 898006...

Page 14: ...ycles per year plus 30 cycles during comissioning Max storage time 12 months at 5 C to 25 C 8 4 Accu LiFePO4 Capacity 1 5 Ah International designation IFpR 19 66 Battery voltage cell 3 2 V Cell type 18650 Case temperature range to ensure 4 years design life 5 C to 55 C 6 years design life 5 C to 45 C 8 years design life 5 C to 35 C Max short term temperature reduced life time 70 C Max number disch...

Page 15: ...operation The Black Box can be read out with the masterCONFIGURATOR and deviceANALYSER via DALI and NFC In order to allow a safe detection of a battery replacement through the Black Box data recording follow the below described process Battery replacement 1 Disconnect mains 2 Disconnect battery 3 Reconnect and disconnect mains while no battery is not connected1 4 Connect new battery 5 Connect main...

Reviews: