Additional accessories
Grease trap
•
Best practice indicates that a grease trap gets fitted before the Tricel Vitae, particularly in
applications where high quantities of grease/oil exist in the wastewater.
•
For the grease trap tp continue to perform effectively, it must be
monitored/maintained on a regular basis and emptied when required.
Warning
If high levels of grease/oil are present within the Tricel Vitae, the plant will not
achieve the required treatment quality and it will reduce the lifespan of plant
components.
Sampling chamber
•
Best practice indicates that a sampling chamber is fitted after every Tricel Vitae to allow
easy access for sampling purposes.
•
Care should be taken to ensure that the sampling apparatus does not come into contact with
the pipework or walls of the sampling chamber to avoid contamination of the sample.
•
Ensure that the outlet is installed high enough in the sampling chamber to allow for the
required sampling volume to be retained in the bottom of the sampling chamber.
•
The inlet/outlet pipework installed in the sampling chamber must be minimum diameter of
110mm.