FMS-2000M
LIT-12013580
18
Each installed pressure sensor correlates to a different room. Admin level users can set up key parameters for each of the monitored
rooms. These include isolation mode, the ability to name the room or parameter, and the ability to set up the door switch if you install it.
When you set up multiple rooms, swipe the screen and complete the following steps for each room.
Naming the device or parameter
If you monitor more than one room, the name that you input appears at the top of each room tile on the home screen.
1. On the home screen, tap the
Settings
icon to enter the settings menu.
2. To view rooms settings, tap
Room
.
3. On the room screen, tap the
Name
arrow.
4. Enter a name. It can be up to 14 characters in portrait mode and up to 16 characters in landscape mode.
5.
To confirm the name, tap the
Checkmark
icon.
Changing the isolation mode
Isolation mode controls the isolation mode options that are available in the restricted level user’s menu and in the isolation mode quick
link on the home screen. The isolation mode quick link is only available on single sensor models.
Isolation mode setup is only available for the first monitored room. Secondary rooms do not have an isolation mode quick link option.
However, you can adjust the alarm limits to correlate with a positive or negative isolation mode.
For isolation mode, Admin level users can choose from the following configurations:
•
Positive and neutral
•
Negative and neutral
•
Positive, negative, and neutral
To change the isolation mode, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the settings menu.
2. To view room settings, tap
Room
.
3. To adjust the isolation mode, expand
Isolation Mode
and choose from the following options:
• Positive Only
• Negative Only
• Positive and Negative
4. To save the new settings, collapse
Isolation Mode
.
Configuring the door switch
If you install a door switch, you can enable the door switch, adjust the switch type, and adjust the alarm delay. The door switch reduces
false positive alarms each time the door opens. Instead, the audible alarm is silent and a yellow warning screen appears and the 360°
Safety Halo flashes yellow. The switch type setting configures the monitor for a normally open or normally closed door switch.
To configure the door switch, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the settings menu.
2. To view room settings, tap
Room
.
3. On the room screen, tap the arrow next to
Door Switch
.
4. On the door switch screen, tap the toggle button to turn the door switch on.
5. Expand
Switch Type
and choose from the following options:
• Normally Open
• Normally Closed
6.
To confirm the settings, collapse
Switch Type
.
Setting up a delay
When you install a door switch, the FMS-2000M can alert the facility staff whenever a person opens the door. The 360° Safety Halo
flashes yellow and the display presents a warning screen with a yellow background. When the door closes, the delay prevents an
audible alarm until the room returns to normal operating pressure. The door switch delay has a maximum duration of 240 seconds.
To set up a delay, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the settings menu.
2. To view digital input settings, tap
Digital Input
.
3. On the Digital Input 1 screen, expand
Delay
and move the slider to adjust the duration of the delay.
4.
To confirm the settings, tap the
Checkmark
.
Network variables
The FMS-2000M can read network variables over the BMS and display the network variables on the home screen. If you wire the
monitor to the BMS in accordance with the BACnet objects below, the network variable automatically appears on the home screen.
Room setup