TriangleTube PTRKIT112 Manual Download Page 2

Gas Valve Replacement Kit

Prestige Solo 399 

2

PRESTIGE 399 BOILER INSTRUCTIONS:

1. Turn power to the unit “OFF”

2. Shut off the gas supply to the boiler at the main

manual shut off valve.

3. Remove the front jacket panel.

4. Remove the wires to the gas valve.

5. Disconnect  the  gas  supply  piping  inside  the

PRESTIGE at the union located just before the
gas valve.

6. Remove  the  4  screws  on  the  top  of  the  gas

valve,    securing  the  gas  valve  outlet  extension
pipe to the valve, see Fig. 2.

7. Remove  the  gas  valve  from  the  PRESTIGE

unit.

8. Remove the 4 screws securing the gas valve sup-

ply piping adapter to the gas valve, see Fig. 2.

9. Remove the O-rings in the gas valve supply pip-

ing adapter and gas valve outlet extension pipe.

10. Install the gas valve supply piping adapter and

O-Ring  gasket  on  the  new  gas  valve  using  4
screws supplies in kit. Ensure screws are tight.

11. Install the new gas valve and O-Ring gasket to

the gas valve extension using the 4 screws sup-
plies in kit. Ensure screws are tight.

12. Reconnect  the  gas  supply  piping  using  two

wrenches. Open the manual gas shut off valve
to  check  and  test  all  gas  connections  for  leaks
before  placing  the  PRESTIGE  unit  back  into
operation.  Repair leaks if found.

Do  not  check  for  gas  leaks  with  an  open
flame. Use a bubble test. Failure to check for
gas  leaks  can  cause  severe  personal  injury,
death or substantial property damage

13. Reconnect the wires to the gas valve, see Fig. 3.

14. Reposition  the  control  module  panel  and  reat-

tached the front jacket panel.

15. Turn  the  electrical  power  “ON”  to  the  PRES-

TIGE to return the unit back into service.

WARNING

2

1

3

Fig. 2:  Prestige 399 Gas Valve Assembly

1. Gas Valve
2. Gas Valve Supply Piping Adapter
3. Gas Valve Outlet Extension Pipe