background image

Prestige

Venturi Replacement 

4

1.  Press the round INSTALLER button.  

DHW Demand

Target = 186°F

Installer Button

Fig. 5:  Navigation Buttons

2.  Enter the installer access code “054” by using the 

LEFT and RIGHT buttons to select a digit and the UP 

and DOWN buttons to change the digit.  Press the 

OK button to enter the access code.

3.  Press the RIGHT button to highlight the Manual 

Operation icon then press the OK button.

4.  Press the OK button while the FAN icon is high-

lighted to manually fire the burner and power the 

CH1 circulator (see Fig. 6)

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH2

FAN

DHW

CH1

Manual Operation

Released

Off

Off

Off

DHW

FAN

CH1

CH2

Fig. 6:  Manual Operation

 

NOTICE

An adequate CH load must be present to dissipate the heat 

generated during the combustion test.  If an adequate CH 

load is not available an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable 

the DHW circulator.

5.  Press the RIGHT button to adjust the firing rate to 

100% (high fire). Hold down the RIGHT button to 

rapidly increase the firing rate.

6.  If the combustion levels during high fire are outside 

the recommended combustion settings adjust the 

THROTTLE SCREW using a flat-blade screwdriver as 

follows:

Counter-clockwise adjustment of the THROTTLE SCREW 

at High Fire (100% firing rate):

 

O2 decreases and CO2  increases

Clockwise adjustment of the THROTTLE SCREW at High 

Fire (100% firing rate):

 

O2  increases and CO2 decreases

7.  Once the combustion level is set at high fire, manu-

ally place the boiler into low fire mode by pressing 

the LEFT button to adjust firing rate down to 1% 

(low fire) to verify low fire combustion settings.

8.  If the combustion levels (O

2

 & CO

2

) during low fire 

are outside the recommended combustion set-

tings in Tables 2, contact Triangle Tube Technical 

Support Department for assistance.

9.  Press the OK button while the fan icon is highlight-

ed to shutdown the burner.

10. 11. Press the LEFT or RIGHT button to highlight the 

home screen icon to exit the service mode.

11. Replace the front jacket panel and secure with 

screws.

12. Turn on the electrical power supply to the Prestige 

boiler and return the unit back to service. 