1.0 Installation of the Propane Orifice

1.   Turn off the electrical power supply to the boiler.

2.   Close the manual gas shut off valve to the unit.

3.   Remove  the  front  panel  of  the  Prestige  by

removing the screws along the bottom edge of

the unit.  Pull the bottom of the panel forward

and then lift up to remove the front panel from

the unit.

4.   Remove the air inlet elbow (Fig 1, Item 1) from

the venturi using a twist and pull motion.

5.   Remove  four  (4)  electrical  plugs    and  one  (1)

ground wire connection from gas valve.

6.   Disconnect  the  gas  supply  piping  inside  the

Prestige  enclosure  at  the  brass  union  located

just above the gas valve.  See Fig. 1.

7.   Remove the four (4) T-25 Torx head screws used to

mount the gas supply piping to the bottom of the gas

valve.  Do not discard the screws.  Remove the gas

valve assembly from the gas piping.  See Fig. 1.

8.   Remove  the  four  (4)  T-25  Torx  head  screws

attaching the brass union collar to the top of the

gas valve.  Do not discard the screws.  Remove

the brass natural gas orifice from the underside

of the brass union collar.  See Fig. 2.

9.   Install  the  appropriate  brass  propane  orifice

from  Table  1  in  the  gasket  between  the  brass

union collar and the venturi.  The rubber o-ring

must remain attached to the brass union collar.

See Fig. 2.

1.   Air Inlet Elbow

2.   T-25 Torx  Head  Screws  (Gas  Valve  to  Gas

Piping)

3.   Gas Valve

4.   Brass Union

Fig. 1:  Prestige Gas Valve/Piping Assembly

2

3

4

1

Fig. 2:     Orifice Location

1.   T-25 Torx Head Screws (Union to Gas Valve)

2.   Gas Valve

3.   Orifice

4.   Orifice O-Ring

Table 1:  Propane Gas Orifice 

2

1

3

4

Model

Orifice Size

Solo 299/399

0.315 inch (8.0 mm)

Summary of Contents for Prestige SOLO 299

Page 1: ...ting rating label DO NOT affix the new label over the existing rat ing label Add propane conversion labeling to the gas valve These instructions cover NG to LP conversion for ACVMax controlled Prestige Solo 299 399 boilers only Each kit is supplied with one orifice suitable for use with that particular boiler model NOTICE NOTICE WARNING WARNING Indicates a potentially hazardous situation which if ...

Page 2: ...T 25 Torx head screws used to mount the gas supply piping to the bottom of the gas valve Do not discard the screws Remove the gas valve assembly from the gas piping See Fig 1 8 Remove the four 4 T 25 Torx head screws attaching the brass union collar to the top of the gas valve Do not discard the screws Remove the brass natural gas orifice from the underside of the brass union collar See Fig 2 9 In...

Page 3: ...brass union and the gas supply piping Retighten the union just above the gas valve and install the four 4 T 25 Torx head screws to attach the gas supply pip ing to the gas valve 12 Reconnect the gas valve electrical connections as shown in Fig 3 13 Open the manual gas shut off valve Before placing the Prestige boiler back into operation check and test all gas connections for leaks Repair leaks if ...

Page 4: ...ical Support Department Failure to comply with this requirement can result in substan tial property damage serious injury or death The gas valve outlet pressure is factory set to the correct value and does not require field adjust ment or measurement Measurement or adjust ments could result in damage to the gas valve and can result in substantial property damage serious injury or death 2 Press the...

Page 5: ...ases Clockwise adjustment of the THROTTLE SCREW at High Fire 100 firing rate O2 increases and CO2 decreases 8 Once the combustion level is set at high fire manually place the boiler into low fire mode by pressing the LEFT button to adjust firing rate down to 1 low fire to verify low fire com bustion settings 9 If the combustion levels O2 CO2 during low fire are outside the recommended combus tion ...

Reviews: