background image

Prestige

Display Module  Replacement 

3

Fig. 5:  Heating Settings

6.  Record all CH Settings in Table 1. Once completed, 

press the 

RIGHT

 button to highlight the Previous  

Screen icon, then press the OK button.

7.  Press the 

RIGHT

 button to highlight the DHW Set-

tings icon then press the OK button.

Fig. 6:  DHW Settings

8.  Press the 

UP

 and 

DOWN

 buttons  to scroll thru  the 

various settings and record all DHW Settings in Ta-

ble 1. Once completed, press the 

RIGHT

 button to 

highlight the Previous Screen icon, then  press the 

OK button.

Fig. 7:  DHW Settings

9.  Press the 

DOWN

 button to highlight the Boiler Set-

tings icon if present icon, then press the OK button.

10. Press the 

UP

 and 

DOWN

 buttons  to scroll through  

the various settings and record all Boiler  Settings 

in Table 1. Once completed, press the 

RIGHT

 but-

ton to highlight the Previous Screen icon, then 

press the OK button.

NOTICE

Perform the following steps if the Instinct is part of a Cascade 

System or the System Temperature Sensor is being used on a 

single Instinct.

11. Press the 

RIGHT

 then 

DOWN

 buttons to highlight 

the Previous Screen icon, then press the OK button.

12. Press the 

RIGHT

 then 

DOWN

 buttons to highlight 

the Cascade icon, then press the OK button.

13. Press the 

RIGHT

 button to highlight the Cascade 

Settings icon, then press the OK button.

14. Press the 

UP

 and 

DOWN

 buttons to scroll thru the 

various settings, and record all Cascade Settings in 

Table 1.

3.  Remove Display Module

1.  Turn the electrical power “OFF”. 

2.  Remove the front jacket panel by removing the 

screws on the bottom of the panel. Pull the pan-

el out and up to remove the panel. Do not discard 

these screws as they will be reused. 

3.  Pull the two retaining tabs on top of the display 

module case to remove the cover. The cover will 

open up. 

Fig. 8:  Display Module

4.  Remove the yellow molex connection from the 

back of the display module. 

Summary of Contents for Prestige PARKIT101

Page 1: ...ore pro ceeding to avoid possible electrical shock and scald hazard Failure to do so can cause severe personal injury or death WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer ser vice technician only Read all instructions before proceeding Follow instructions in proper order Each Kit Includes Display ...

Page 2: ...s and document the boiler s settings This will ensure any settings revised from factory defaults are transferred to the new module s Use Table 1 to record the existing settings Do not revise any settings when recording settings 1 To access the parameter screen press the round in staller button as shown in Fig 1 Fig 1 Installer Button 2 Enter the installer access code 054 by using the LEFT and RIGH...

Page 3: ... Screen icon then press the OK button NOTICE Perform the following steps if the Instinct is part of a Cascade System or the System Temperature Sensor is being used on a single Instinct 11 Press the RIGHT then DOWN buttons to highlight the Previous Screen icon then press the OK button 12 Press the RIGHT then DOWN buttons to highlight the Cascade icon then press the OK button 13 Press the RIGHT butt...

Page 4: ...nel to the boiler 6 Turn power to the unit ON and return the boiler to service 5 Programming new Control Board 1 Follow the instructions in step 2 to gain access to the installer menu 2 Go to boiler settings and click appliance setting as seen in Fig 9 and Fig 10 Fig 9 Installer Menu Fig 10 Appliance setting 3 The required code is written on the data plate lo cated at the side of the boiler Use th...

Page 5: ...ff Off 78 F 25 C Circulation Pump Permanent Disabled CH Post Pump Time 5 Minutes Off 20 Minutes Freeze Protection Enabled Frost Protection Setpoint 22 F 30 C 22 F 30 C 50 F 10 C Parallel Shift Value 0 F 0 C 0 F 0 C 144 F 80 C CH Call Blocking 2 Minutes 0 Minutes 30 Minutes DOMESTIC SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EXISTING SETTING DHW Operation Enabled Demand Type Thermostat...

Page 6: ...Relay On Lockout Blocking and Warning Pump PWM Minimum 30 1 100 Ignition Level Varies by model Mix Zone High Limit 114 F 45 C 68 F 20 C 176 F 80 C Appliance Setting Varies by model CASCADE SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING EXISTING SETTING Stage Delay 60 Seconds 0 Seconds 255 Seconds Minimum Firing Rate 18 0 100 Max Firing Rate Varies by model 0 MBH 0kW 869 MBH 255kW CH DHW B...

Reviews: