Entering Installer access code
3
EnTERInG InSTaLLER accESS codE
Installer
Button
The
InSTaLLER
button (the small round button) provides the installing contractor with full access
to all available features after entering an access code
.
ENTER INSTALLER
ACCESS CODE
05[4]
Entering installer access code procedure
1. Press the round
InSTaLLER
button.
2. Enter the installer access code “054” by using the
LEfT
and
RIGHT
buttons to select a digit and the
UP
and
doWn
buttons to change the
digit. Press the
oK
button to enter the access code.
3. The Installer Menu will be displayed after successfully entering the
access code. The Home Screen will be displayed if the access code is
not entered correctly.
Entering the installer access code allows the installer to make adjust-
ments for 30 minutes. after 30 minutes, the access code will need to
be entered again to make any adjustments.
The Installer Menu is divided into four sections:
1. CH & DHW Settings
– Allows the installer to adjust the boilers
central / space heating and domestic hot water settings for the applica-
tion. See pages 5 through 18.
2. Manual Operation
– The burner and circulators can be manually
enabled for testing. See page 41.
3. Reset All Settings
– Resets all CH, DHW, and Cascade Settings
back to the factory defaults. See pages 19 through 20.
4. Cascade – Settings
Allows the installer to setup, adjust, and mon-
itor the Cascade System. See pages 21 through 38.