Challenger Blower 

Replacement Kit

2

1.  Removal of Blower

1.  Turn off power to the unit at the main service 

switch.

2.  Close the external gas shut off valve to the appli-

ance. 

3.  Remove the front panel by flipping down the dis-

play cover and loosening the (2) Phillips head 

screws at the control panel as per Fig. 1. Pull bot-

tom of front panel forward to remove.

Fig. 1:  Control Panel Screws

4.  Disconnect the two wire harness plugs from the 

blower motor.  

BEST PRACTICE

For ease of service, remove the vent pipe between the 

vent adapter and the condensate drain pan before re-

moving the blower. To remove the vent pipe, loosen the 

vent pipe retaining ring attaching it to the condensate 

pan then slide the pipe up and out of the condensate 

pan.  Pull the vent pipe out and down to remove.

5.  Loosen the gas pipe brass nut at the gas valve.  Set 

aside the orifice and o-ring for reinstallation. See 

Fig. 2

Fig. 2:  Gas Orifice location

NOTICE

Do not discard the gas orifice and gasket as they will be re-

used. 

6.  Remove the (2) M5 flange nuts attaching the blow-

er to the burner assembly with an 8 mm socket or 

wrench. 

7.  Remove the blower assembly from the Challenger 

by pulling downward and out. 

NOTICE

If the blower gasket sticks to the burner assembly, use a flat 

blade putty knife to remove any gasket material. Make sure 

not to scratch the mating surface on the burner assembly. 

8.  For Challenger models 85 and 105 only, remove the 

blower orifice and save to be reinstalled. 

See Fig. 3

.

Summary of Contents for CCRKIT32

Page 1: ... injury or death WARNING For your safety the boiler may be extremely hot Ensure the boiler has properly cooled prior to ser vicing Failure to do so can cause severe personal injury WARNING Failure to follow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer ser vice technician only Read all instructions before proceeding Follow i...

Page 2: ...retaining ring attaching it to the condensate pan then slide the pipe up and out of the condensate pan Pull the vent pipe out and down to remove 5 Loosen the gas pipe brass nut at the gas valve Set aside the orifice and o ring for reinstallation See Fig 2 Fig 2 Gas Orifice location NOTICE Do not discard the gas orifice and gasket as they will be re used 6 Remove the 2 M5 flange nuts attaching the ...

Page 3: ...the venturi and gas pipe are properly seated 3 Insert the venturi clip into the blower housing En sure the venturi clip is holding the venturi and gas pipe in place by lightly pulling on the gas pipe NOTICE Do NOT force the clip into a flush fit with the blower surface Fig 4 Venturi assembly installation 4 Seat the blower orifice if required and blower outlet gasket onto the blower flange Position...

Page 4: ... turn to service 12 Perform a combustion analysis by measuring CO2 or O2 and CO during both low and high firing rates The combustion readings must be within the range listed in Table 1 The CO level must not exceed 100 ppm for natural gas and 150 ppm for propane gas when combustion is correct Perform the following procedure to manually place the burner into high fire Press both the and buttons simu...